4. System Controller

TD831078

III - 26

3

System controller / SHA-KC64UG

Example of central control with system controller (individually controlled)

New control wiring system (S-net link system)

New control wiring system (S-net) allows connection of as many as total of 94 units (64 Indoor unit

+30 Outdoor unit) to a single contorl line (non-polar twin-line main bus).

The main bus is twin-core and non-polar for easier wiring.

Using concurrently as remote controller, system controller can control maximum up to 64 indoor units (or

groups) individually.

The system without remote controller can be formed.

Maximum up to 2 system controllers (1 main, 1 sub) can be installed.

It can separate the 64 indoor units into 4 zones and control each zone individually.

Maximum up to 16 groups can be registered to each zone.

Collective control and individual group (unit) control can be performed also.

Alarm and operation output for an external collected signal is available (potential free contact) DC24V

Max. 1A.

Input terminal for collective operation on / off is available.

Outdoor unit

Remote
controller

System
controller
(main)

System without
Remote controller

Group
control

Outdoor unit

2157_M_I

System
controller
(sub)

Remote
controller

Group
control

Group
control

Remote
controller

TD831138-02_W-2WAY.indb 38

2007/07/26 14:31:43