Siemens IK PI · 2004

6/101

AS-Interface Slaves

Modules with special functions

Earth fault detection modules

6

Technical specifications

1) U

Aux

should be protected with a slow-action 2 A fuse.

2) For increasing the relay endurance with inductive loads,

a protective circuit with free-wheeling diodes is recommended.

Earth fault detection module

With screw-type terminal connection

With Cage Clamp terminal connection

3RK1 408-8KE00-0AA2

3RK1 408-8KG00-0AA2

Total current input in mA

£ 40

Polarity reversal protection

Built-in

Earth fault

10% U

AS-i

£ U

GND

£ 90% U

AS-i

Low signal range

I

IN

in mA

£ 1.5

High signal range

U

IN

in V

³ 10

I

IN

in mA

³ 6

Current carrying capacity

1

)

• DC 12 in A

1 (max. 2 per module)

• DC 13 in A

500 (24 V)

2

)

• DC 13 in mA

200 (48 V)

2

)

Operating cycles DC 12

2

´ 10

6

Rated operating voltage range in V 24 to 48 DC

Degree of protection

IP20

Dimensions (H x W x D) in mm

102

´ 22.5 ´ 92

Rated temperature in °C

25

Ambient temperature in °C

-25 to +70

Storage temperature in °C

-40 to +85

Addressing

The module does not require an individual AS-Interface address

Connection

Screw-type terminal connection

Spring-loaded terminal connection

Conductor cross-sections in mm

2

• Solid

--

2

´ (0.25–1.5)

• Finely stranded with end sleeve

--

2

´ (0.25–1)

• Finely stranded without end

sleeves

--

2

´ (0.25–1.5)

• AWG conductors,

solid or stranded

--

AWG 2

´ (24–16)

Note

If repeaters are used, each AS-Interface segment needs its own earth fault detection module
(number of AS-Interface power supply units = number of earth fault detection modules)