As-interface slaves, I/o modules for operation in the field – Siemens ISI EN 50295 User Manual

Page 68

Advertising
background image

Siemens IK PI · 2004

6/68

AS-Interface Slaves

Digital I/O modules IP67 - application modules

I/O modules for operation in the field

6

Technical specifications (continued)

4 outputs

Relay

PNP transistor

NPN transistor

PNP transistor

3RG9 001–0AB00

39 001–0AL00

3RK1 100–1CQ01–0AA3

3RG9 001–0CB00

Slave type

Standard slaves

Operational voltage in accordance
with AS-Interface specification in V

26.5 to 31.6

Total current input in mA

£ 60

£ 50

£ 60

Output connection

PNP

NPN

PNP

Outputs

• Type of output

Relay

Electronics

• Current carrying capacity per

output in A DC 12 / DC 13 typ.

1 (DC 12) 0.5 (DC 13 24
V)

1

• Maximum summation current

per module in A

2

• Short-circuit protection

Built-in

• Inductive interference protection

(free-wheeling diode)

Built-in

• External 24 V DC supply voltage

Via M12 connector on the end face of the module

Via FK-E or PG-E coupling module

Watchdog

Not available

Built-in

Connection of AS-Interface

EMI

EEMI

I/O configuration

8

ID code

0

1

0

Assignment of data bits

• Socket 1

Output (D0)

PIN4 = OUT1 (D0)
PIN2 = OUT2 (D1)

Output (D0)

• Socket 2

Output (D1)

PIN4 = OUT2(D1)

Output (D1)

• Socket 3

Output (D2)

PIN4 = OUT3(D2)
PIN2 = OUT4(D3)

Output (D2)

• Socket 4

Output (D3)

PIN4 = OUT4(D3)

Output (D3)

AS-Interface certificate

Yes

Approvals

UL, CSA, ship building

Degree of protection

IP67

Ambient temperature in °C

-25 to +85

Storage temperature in °C

–40 to +85

Number of I/O sockets

4

Display of outputs

Yellow LED

AS-Interface display

Green LED

Red/yellow/green LED

Green LED

Diagnostics

Without LED

"AS-i" LED:
green = OK
red =
no data communication
flashing red/yellow =
null address
flashing red =
overload sensor

Without LED

Connection

Via contact pin on the FK or Pg coupling module

Via contact pin on the FK-E or Pg-E coupling module

Note 1

To supply the output circuit, an external supplementary supply (AUX POWER) of 20 to 30 V DC is necessary.
The supplementary supply must comply with VDE 0106 (PELV), Safety Class III.

Note 2

In the event of a commu-
nications failure, the relay
outputs remain in the
current switching state.

Advertising