As-interface slaves, I/o modules for operation in the field – Siemens ISI EN 50295 User Manual

Page 67

Advertising
background image

Siemens IK PI · 2004

6/67

AS-Interface Slaves

I/O modules for operation in the field

Digital I/O modules IP67 - application modules

6

Technical specifications (continued)

2 x (1 input/1 output)

PNP transistor
3RG9 001–0AJ00

Slave type

Standard slaves

Operational voltage in accordance
with AS-Interface specification in V

26.5 to 31.6

Total current input in mA

£ 270

Input connection

PNP

Inputs

• Sensor supply via AS-Interface

Short-circuit and overload proof

• Voltage range in V

20 to 30

• Load rating for all inputs in mA

200

• Connection of sensors

2-wire system

• Switching level High in V

³ 10

• Input current Low/High in mA

£ 1.5 / ³ 5

Outputs

• Type of output

Electronics

• Current carrying capacity per

output in A DC 12 / DC 13 typ.

0.2

• Maximum summation current

per module in A

0.2

• External supply voltage

Not required

• Short-circuit protection

Built-in

• Inductive interference protection

(free-wheeling diode)

Built-in

• External 24 V DC supply voltage

The outputs are supplied via the
yellow AS-Interface cable

• Watchdog

Built-in

Connection of AS-Interface

EMI

I/O configuration

3

ID code

F

Assignment of data bits

• Socket 1

Input D0 and output D2

• Socket 2

--

• Socket 3

Input D1 and output D3

• Socket 4

--

AS-Interface certificate

Yes

Approvals

UL, CSA, ship building

Degree of protection

IP67

Ambient temperature in °C

-25 to +85

Storage temperature in °C

-40 to +85

Number of I/O sockets

2

I/O display

Yellow LED

AS-Interface voltage display

Green LED

Diagnostics

Without LED

Connection

Via contact pin on the FK or Pg
coupling module

Note

The black AS-Interface cable is
not required

4-fold distributor passive
without LED

3RG9 001-0AD00

Function

The passive 4V application mod-
ule is used for connecting the
intelligent I/O to the AS-Interface

Operating voltage in V

26.5 to 31.6 DC (AS-Interface)

Voltage range in V

20 to 30 DC

Current load for all total in A

2

Socket assignment

1 = AS-i ”+“3 = AS-i ”–“

Connection

4 x M12 socket for connecting AS-
Interface (Sensors/actuators)

Degree of protection

IP67

Ambient temperature in °C

–25 to +85

Non-operating temperature in °C

–40 to +85

Number of M12 sockets

4

Connection

Via contact pin on the FK or Pg
coupling module

Advertising