Siemens IK PI · 2004

6/90

AS-Interface Slaves

Module F90

I/O modules for operation in IP20 control cabinet

6

Technical specifications (continued)

4 inputs/4 outputs

2 A, floating
screw-type terminals

Combicon connection

3RG9 002-0DC00

3RG9 004-0DC00

Slave type

Standard slaves

Operational voltage in accordance
with AS-Interface specification in V

26.5 to 31.6

Total current input in mA

£ 30

Input connection

PNP

Inputs

• Sensor supply via AS-Interface

Short-circuit and overload proof

• Voltage range in V

20 to 30

• Load rating for all inputs in mA

200

• Connection of sensors

2- and 3-wire system

• Switching level High in V

³ 10

• Input current Low/High in mA

£ 1.5 / ³ 5

Outputs

• Type of output

Electronics

• Current carrying capacity in A

DC 12 / DC 13 typ.

2

• Total current of all outputs in A

6

• Short-circuit protection

Built-in

• Inductive interference protection

(free-wheeling diode)

Built-in

• External voltage supply 24 V DC

Via screw terminal

Via Combicon pin connector

Watchdog

Built-in

I/O configuration

7

ID/ID2 code

0/F

Assignment of data bits

• Data bit D0

IN1/OUT1

• Data bit D1

IN2/OUT2

• Data bit D2

IN3/OUT3

• Data bit D3

IN4/OUT4

AS-Interface certificate

Yes

Approvals

UL, CSA, ship building

Degree of protection

IP20

Ambient temperature in °C

-25 to +70

Storage temperature in °C

-40 to +85

Displays

• Inputs/outputs

Yellow LED

• AS-i voltage

Green LED

Connection

Via screw terminal

Via Combicon pin connector

Addressing

An integrated addressing socket can be used

Note 1

The module has four floating inputs and four floating switching outputs. For the input and output circuits,
an external additional supply of 20 to 30 V according to VDE 0106 (PELV) safety class III is required.

Note 2

To supply the output circuit, an external supplementary supply (AUX POWER) of 20 to 30 V DC is necessary.
The supplementary supply must comply with VDE 0106 (PELV), safety class III.