Siemens IK PI · 2004

6/5

AS-Interface

Introduction

Technical specifications

6

Technical specifications

More information

Please note the operating framework conditions in each case for
the specified SIMATIC NET products (Order No. 6GK..., 6XV1...),
which you will find on the Internet page listed below.

Additional information is available in the Internet under:

http://www.siemens.de/simatic-net/ik-info

Standard

EN 50295

Topology

Bus, star or tree topology
(like electrical installation)

Transmission medium

Unshielded two-wire cable
(2 x 1.5 mm

2

) for data and

auxiliary power

Connection method

Contacting of the AS-Interface
cable using the insulation
displacement method

Permissible cable length max.

100 m w/o repeater/extender
500 m range with repeater/
extender (parallel connection
of repeaters)

Cycle time max.

5 ms with full expansion,
10 ms using A/B method

Number of stations max.

31 slaves accord. to Complete
AS-Interface Spec. V2.0 ;
62 slaves accord. to Complete
AS-Interface Spec. V2.1
(A/B method),
integrated analog value
transmission

Number of binary
sensors/actuators

Max. 124 I/124 O
modules according to spec. V2.0;
Max. 248 I/186 O
modules according to spec. V2.1

Access procedure

Cyclical master-slave polling
method, cyclical acceptance
by host (PLC, PC)

Error correction

Identification and repetition of
faulty messages