As-interface power supply units, Power supply units ip20 – Siemens ISI EN 50295 User Manual

Page 138

Advertising
background image

Siemens IK PI · 2004

6/138

AS-Interface Power Supply Units

Power supply units IP20

6

Technical specifications (continued)

AS-Interface power supply unit

Single Output IP20

With integrated earth-fault detection

6EP1 354-1AL01

3RX9 310-0AA00

Output current in A

7

2.4

Rated input voltage in V

120 to 230 AC

115/230 AC

Input

• Range selection

With variable range input

With changeover switch

• Voltage range in V

93 to 264 AC / 110 to 350 DC

195 to 253 / 102 to 132 AC

• Overvoltage strength

VDE 0160 Limiting curve W2

EN 61 000-4-1

• Mains buffering at I

e

Rated in ms < 20 at 93/187 V

> 20

• Mains frequency rated value I

range in Hz

0/50/60/47 to 63

• Built-in input fuse in A

T 6.3 (not accessible)

T 2

• Recommended circuit-breakers

(IEC 898) in A

From 16, characteristic C or
from 8, characteristic B

From 10, characteristic C

Output

• Stabilized floating DC voltage

acc. to AS-Interface specification

Yes

• Voltage rating U

aRated

in V

30 DC

• Total tolerance

29.5 to 31.6 DC

• Residual ripple in mVpp

(0–10 kHz, AS-i+/AS-i–)

< 300

• Spikes in mVpp

(10–500 kHz, AS-i+/AS-i–)

< 50

• Operational display

Green LED

• Current rating I

a Rated

in A

7

2.4 (power boost: 2.8)

Efficiency/power loss

• Efficiency at U

aRated

, I

aRated

in %

> 85

• Power loss at U

aRated

, I

aRated

in W < 37

10

Protective and monitoring functions

• Overvoltage protection of outputs Yes

No

• Current limitation in A

From approx. 7.4

> 2.8

• Short-circuit protection

Stabilized current characteristic approx. 7.4 A

Yes

Safety

• Primary/secondary isolation

SELV to EN 60 950

• Safety class (EN 60 950/IEC 950) Class I to IEC 536

I

• Degree of protection

IP20 to EN 60 529

IP20

• Approvals

CE, UL/cUL

CE, UL, CSA (in preparation)

EMC

• Emitted interference

EN 50 081-1, EN 55 022 Cl. B

EN 50 081-1

• Noise immunity

EN 50 082-2

Operational data

• Ambient temperature range in °C 0 to +55

-25 to +55

• Transport and storage

temperature range in °C

-25 to +85

-25 to +60

• Humidity class

F to DIN 40 040

Max. 80% rel. humidity

Mechanical data

• Input connection

1 terminal each for 0.5 to 2.5 mm

2

Spring-loaded terminal connection (0.5 to 2.5 mm

2

)

• Output connection AS-i +

3 terminals for 0.5 to 2.5 mm

2

Spring-loaded terminal connection (0.5 to 2.5 mm

2

)

• Output connection AS-i -

3 terminals for 0.5 to 2.5 mm

2

Spring-loaded terminal connection (0.5 to 2.5 mm

2

)

• Output connection shield S

2 terminals for 0.5 to 2.5 mm

2

Spring-loaded terminal connection (0.5 to 2.5 mm

2

)

• Dimensions (W x H x D) in mm

200

´ 125 ´ 135

92

´ 110 ´ 136

• Mounting

Snap-on mounting onto standard rail DIN EN 50 022-
35

´ 15 mm and S7 rail

Snap-on mounting onto standard rail DIN EN 50 022-
35 x 7.5 mm

Special function

-

Integrated 3RK1 408-8KE00-0AA2 earth fault detec-
tion module and isolation of the AS-Interface voltage
with corresponding circuit

Advertising