As-interface, As-interface safety at work, As-interface safe compact modules – Siemens ISI EN 50295 User Manual

Page 14

Advertising
background image

Siemens IK PI · 2004

6/14

AS-Interface

AS-Interface safe compact modules

AS-Interface Safety at work

6

Schematics

Logical assignments

K45F Safe Compact Module

If only one single-channel switch will be connected to the mod-
ule, this must be connected to Channel 1. The second channel
must be bridged. This can be performed with the M12 connector
3RK1901-1AA00 on Socket 2.

Pin 3 of Socket 1 is connected to Pin 1 of Socket 2 and Pin 4 of
Socket 1 is connected to Pin 2 of Socket 2. If both socket pairs
are assigned, the inputs are linked.

K60F Safe Compact Module

Pin 3 of Socket 1 is connected to Pin 1 of Socket 2 and Pin 4 of
Socket 1 is connected to Pin 2 of Socket 2. If both socket pairs
are assigned, the inputs are linked.

Socket

Assignment / data sheet / function

1

Pin 1 and Pin 2: affects bits D0 and D1 = Channel 1
Pin 3 and Pin 4: affects bits D2 and D3 = Channel 2
Pin 5 not assigned

2

Pin 1 and Pin 2: affects bits D2 and D3 = Channel 2
Pin 5 not assigned

3

Unused

4

Unused

²

1

2

3

4

ADDR

1

2

3

4

G_NSA0_XX_00355

Socket

Assignment / data sheet / function

1

Pin1 and Pin 2: affects bits D0 and D1 = Channel 1
Pin 3 and Pin 4: affects bits D2 and D3 = Channel 2
Pin 5: unused

2

Pin 1 and Pin 2: affects bits D2 and D3 = Channel 2
Pin 5: unused

3/4/7 and
8

Not assigned, factory sealed

5

Pin 4: Output 1
Pin 3: --
Pin 5: Ground
Pin 1 and Pin 2: unused

6

Pin 4: Output 2
Pin 3: --
Pin 5: Ground
Pin 1 and Pin 2: unused

3

4

2

N S A _ 0 0 3 5 8

1

3

7

5

1

4

8

6

2

Advertising