AS-Interface Slaves

I/O modules for operation in the field

Digital I/O modules IP67 - application modules

6

Technical specifications

4 inputs

2 x 2 inputs

100 mA

200 mA

PNP transistor

NPN transistor

PNP transistor

Standard assignment

Y-II assignment

Y assignment

3RG9 001–0AA00

3RG9 001–0AG00

3RK1 200-0CQ01-0AA3

3RG9 001–0AH00

Slave type

Standard slaves

Operational voltage in accordance
with AS-Interface specification in V

26.5 to 31.6

Total current input in mA

£ 120

£ 250

£ 290

£ 250

Input connection

PNP

PNP

NPN

PNP

Inputs

• Sensor supply via AS-Interface

Short-circuit and overload proof

• Voltage range in V

20 to 30

20 to 27

20 to 30

• Current carrying capacity

for all inputs (T

u

£ 40 °C) in mA

100

200

• Connection of sensors

2- and 3-wire system

2-, 3- and 4-wire system

• Switching level High in V

³ 10

• Input current Low/High in mA

£ 1.5 / ³ 5

Connection of AS-Interface

EMI

Watchdog

--

I/O configuration

0

ID code

0

1

Assignment of data bits

• Socket 1

Input (D0)

PIN4 = IN1 (D0)
PIN2 = IN2 (D1)

Input (D0 and D1)

• Socket 2

Input (D1)

PIN4 = IN2(D1)

--

• Socket 3

Input (D2)

PIN4 = IN3 (D2)
PIN2 = IN4 (D3)

--

• Socket 4

Input (D3)

PIN4 = IN4(D3)

Input (D2 and D3)

AS-Interface certificate

Yes

Approvals

UL, CSA, ship building

Degree of protection

IP67

Ambient temperature in °C

-25 to +85

Storage temperature in °C

–40 to +85

Number of I/O sockets

4

2

I/O display

Yellow LED

AS-Interface display

Green LED

Red/yellow/green LED

Green LED

AS-Interface/diagnostics display

Not available

"AS-i" LED:
green = OK
red =
no data communication
flashing red/yellow =
null address
flashing red =
overload sensor

Not available

Connection

Via contact pin on the FK or Pg coupling module

Advertising