As-interface slaves, Modules with special functions – Siemens ISI EN 50295 User Manual

Page 99

Advertising
background image

Siemens IK PI · 2004

6/99

AS-Interface Slaves

Modules with special functions

Counter modules

6

Technical specifications

Selection and Ordering data

Counter modules

With screw-type terminal connection

With Cage Clamp terminal connection

3RK1 200-0CE03-0AA2

3RK1 200-0CG03-0AA2

Slave type

Standard slaves

Operational voltage in accordance
with AS-Interface specification in V

26.5 to 31.6

Total current input in mA

£ 170

Input

• Sensor supply via AS-Interface

Short-circuit and overload proof

• Assignment

Terminal 7 = +
Terminal 9 = -
Terminal 8 = IN1

• Voltage range in V

20 to 30

• Current carrying capacity in mA

90

• Switching level Low/High in V

£ 5 / ³ 10

• Input current Low/High in mA

£ 2 / ³ 10

I/O configuration

0

ID code

F

AS-Interface certificate

Yes

Approvals

UL, CSA, ship building

Degree of protection

IP20

Ambient temperature in °C

-25 to +70

Storage temperature in °C

-40 to +85

Displays

• AS-i

Green LED on + red LED off = status O.K.
Green LED off + red LED on = no data traffic
Green LED flashing + red LED on = null address
Green LED off + red LED flashing = overload (sensor)

Connection

Screw terminals

Cage Clamp terminals

Conductor cross-sections in mm

2

• Solid

--

2

´ (0.25–1.5)

• Finely standed with end sleeve

--

2

´ (0.25–1)

• Finely stranded without end

sleeves

--

2

´ (0.25–1.5)

• AWG conductors,

solid or stranded

--

AWG 2

´ (24–16)

Design

Order No.

3RK1 200-0CE03-0AA2

3RK1 200-0CG03-0AA2

Counter module

• with screw terminals

3RK1 200-0CE03-0AA2

• with Cage Clamp terminals

3RK1 200-0CG03-0AA2

Advertising