As-interface slaves, I/o modules for operation in the field, Digital i/o modules ip67 - application modules – Siemens ISI EN 50295 User Manual

Page 69

Advertising
background image

Siemens IK PI · 2004

6/69

AS-Interface Slaves

I/O modules for operation in the field

Digital I/O modules IP67 - application modules

6

Technical specifications (continued)

FK coupling module

FK-E coupling module

for 2 x AS-Interface cable (yellow)

for 1 x AS-Interface cable (yellow) and
1 x AS-Interface cable (black)

Standard version

Version with high-grade
steel components and
Viton seals

Standard version

Version with high-grade
steel components and
Viton seals

3RG9 010–0AA00

3RK1 901–1HA00

3RG9 030–0AA00

3RK1 901–1JA00

Operating voltage in accordance
with AS-Interface specification in V

26.5 to 31.6

Loading capability in A

£ 2

Interface

EMI

EEMI

Ambient temperature in °C

-40 to +85

Degree of protection

IP67 (with cover/application module)

Connection technique

Insulation piercing technique for AS-Interface flat cable

Mounting possibilities

For wall and standard rail mounting

Scope of delivery

1

´ coupling module

4

´ shaped seal

3

´ terminating seal

1

´ coupling module

4

´ shaped seal (Viton)

3

´ terminating seal

(Viton)

1

´ coupling module

4

´ shaped seal

3

´ terminating seal

1

´ coupling module

4

´ shaped seal (Viton)

3

´ terminating seal

(Viton)

Special features

--

Integrated high-grade
steel threaded bushings

--

High-grade steel
threaded bushings

Note

Cable baskets are connected electrically in parallel
and are suitable for single T and double T junctions

--

PG coupling module

PG-E coupling module

3RG9 220-0AA00

3RG9 240-0AA00

Operational voltage in accordance
with AS-Interface specification in V

26,5 to 31,6

Loading capability in A

4

Interface

EMI

EEMI

Ambient temperature in °C

-25 to +85

Degree of protection

IP67 (with cover/application module)

Connection technique

Via screw terminals to AS-Interface cable
with top section of module

Via screw terminals to AS-Interface cable and U

Aux

via

male contact connection to top section of module

Mounting possibilities

For wall and standard rail mounting

Supply includes

1

´ PG coupling module

4

´ nuts

2

´ cable gland PG11

3

´ locking bolts

External cable diameter in mm

6 to 10

Conductor cross-section in mm

2

1 to 2.5

Screwed cable gland

Pg11

Note

When using AS-Interface flat cables, shaped PG gaskets are required(3RX9 805-0AA00)

Advertising