6/106

AS-Interface Slaves

AS-Interface compact starters IP65 (400 V AC)

AS-Interface motor starters and IP65/67 load feeders

6

Design (continued)

The load itself and any other compact starters are supplied us-
ing the same connection technique. All the supply and data ca-
bles can thus be laid through the system like a bus. Whereas the
controlgear is switched via the outputs by the 24 V auxiliary
power supply, the inputs are supplied by the AS-Interface data
cable. This principle of separate auxiliary power supplies facili-
tates selective emergency stop concepts.

Addressing

The addressing of the AS-Interface compact starter can still be
used even if it is fully wired, because the module is disconnected
from the AS-Interface network as soon as the addressing con-
nector is inserted.

Function

Display characteristics

Under normal operation, the LEDs on the compact starters indi-
cate the following device states:

LED

AUX PWR

AS-Interface

STATE

1

)

NSA0_00322

Status description

Control signal applied
No auxiliary power
Auxiliary power on
No power for slave electronics
Station address 0
AS-Interface communication absent
AS-Interface communication o.k.

On

States

Flash-

ing

On

On

Flash-

ing

Off

On

Off

LED

RUN

READY

FAULT

NSA0_00323

OVERLOAD

States

Status description

Main circuit on

– Rotary coding switch in position

Tripping REMOTE: Continued ope-

ration when programmed in the user

program
Main circuit off

– Rotary coding switch in position

Tripping LOCAL: Direct shut-off

– Rotary coding switch in position

Tripping REMOTE: Remote shut-off

when programmed in the user

program
Main circuit off

(test finished)
Main circuit off

(test running)
Main circuit on
Main circuit off, e.g. through

– Failure of two phases

– Drawn motor connector

– Supply voltage drop

(< 18 V)

– Simultaneous control of clockwise

and anti-clockwise rotation
Main circuit on with conduction

>_ 20%

n

Unit ready to operate

On

On

Off

On

On

Nor-

mal

flash-

ing

Fast

flash-

ing

Slow

flash-

ing

On

On