Power supply units ip65, As-interface power supply units – Siemens ISI EN 50295 User Manual

Page 141

Advertising
background image

Siemens IK PI · 2004

6/141

AS-Interface Power Supply Units

Power supply units IP65

6

Technical specifications

1) The counterpart is not included in the scope of supply (see accessories).

AS-Interface IP65 power supply unit

Rated input voltage 230 V AC

Rated input voltage 24 V DC

3RX9 311-0AA00

6EP1 632-1AL01

Output current in A

2.4

2.4

Rated input voltage in V

230 AC

24 DC

Input

• Rated input voltage U

e rated

in V

230 AC

24 DC

• Range selection

Changeover contact (internal)

--

• Input voltage range in V

195 to 253

20.4 to 28.8 DC

• Overvoltage resistance

EN 61 000-4-1

35 V DC for max. 500 ms

• Mains buffering at I

e rated

in ms

> 20

> 10

• Mains frequency rated value I range

in Hz

50/60/47 to 63

--

• Input current rating I

e

rated

in A

< 0.5

3.6

• Built-in input fuse in A

T 2 (not accessible)

T 6.3 (not accessible)

Output

• Stabilized floating DC voltage

acc. to AS-Interface specification

Yes

Yes

• Rated output voltage U

a rated

in V

30 DC (AS-Interface)

30 DC (AS-Interface)

• Total tolerance

29.5 to 31.6 V DC

29.5 to 31.6 V DC

• Residual ripple in mVpp

< 300

< 300

• Spikes in mVpp

< 50

< 50

• Operational display

Green LED

Green LED

• Output current rating I

a rated

in A

2.4 (power boost 2.8)

2.4

Efficiency/power loss

• Efficiency at U

a rated

, I

a rated

in %

Approx. 85

> 81

• Power loss at U

a rated

, I

a rated

in W

Approx. 10

< 17

Protection and monitoring functions

• Output overvoltage protection

No

--

• Current limitation in A

> 2.8

From approx. 2.9

• Short-circuit protection

Yes

Stabilized current approx. 2.9 A

Safety

• Primary/secondary isolation

Yes (SELV to EN 60 950)

Yes (SELV to EN 60 950)

• Safety class

Class I to IEC 536

Class I to IEC 536

• Degree of protection

IP65

IP65

• Approvals

CE, UL, CSA (in preparation)

CE, UL, ship building

EMC

• Emitted interference

EN 50 081-1

EN 50 081-1, EN 55 022 Cl. B

• Noise immunity

EN 50 082-2

EN 50 082-2

Operational data

• Ambient temperature range in °C

-45 to +55

-25 to +55

• Transport and storage

temperature range in °C

-45 to +60

-25 to +85

• Humidity class

Max. 80% rel. humidity

F to DIN 40 040

Mechanical data

• Input connection

Amphenol device socket

Circular connector 0.5 to 2.5 mm

21

)

• Output connection AS-i +

AS-i+/AS-i: via yellow AS-Interface cable

500 mm 3-wire conductor AWG 14

• Output connection AS-i -

FK line adapter

500 mm 3-wire conductor AWG 14

• Output connection Ground

--

500 mm 3-wire conductor AWG 14

• Dimensions (W x H x D) in mm

105

´ 155 ´ 117

224

´ 80 ´ 57

• Mounting

Mounting onto standard rails
DIN EN 50 022-35 x 7.5

Wall mounting

Special function

--

--

Accessories

--

6-pole connector for input voltage (6ES5 760-2CA11)
and AS-Interface coupling module PG
(3RG9 220-0AA00) must be ordered separately

Advertising