As-interface slaves, I/o modules for operation in ip20 control cabinet, Slimline – Siemens ISI EN 50295 User Manual

Page 84

Advertising
background image

Siemens IK PI · 2004

6/84

AS-Interface Slaves

SlimLine

I/O modules for operation in IP20 control cabinet

6

Technical specifications (continued)

4 inputs/4 outputs

4 inputs/4 outputs

Spring-loaded connection

Spring-loaded connection

Standard slave

Standard slave

2- and 3-wire

2- and 3-wire

PNP transistor (1 A)

Relay

3RK1 402-3CG01-0AA2

3RK1 402-3CG00-0AA2

Total current input in mA

£ 40

£ 270

Inputs

• Sensor supply via AS-Interface

Short-circuit and overload withstand capability

Short-circuit and overload withstand capability

• Voltage range in V

20 to 30

20 to 30

• Current carrying capacity

for sensor supply in mA

200

200

• Connection of sensors

2- and 3-wire system

2- and 3-wire system

• Switching level High in V

³ 10

³ 10

• Input current Low/High in mA

£ 1.5 / ³ 5

£ 1.5 / ³ 5

Outputs

• Type of output

Electronics

Relay

• Current carrying capacity

per output in A DC 12 / DC 13 typ.

1

--

• Maximum summation current

per module in A

4

--

• Short-circuit protection

Built-in

External back-up fuse 6 A gL/gG

• Inductive interference protection

(free-wheeling diode)

Built-in

Not applicable

• Polarity reversal protection

Built-in

Built-in

• External 24 V DC supply voltage

Sensor supply:
Terminal 13 = U_s+
Terminal 19 = U_s–
Actuator supply:
Terminal 14 = L+
Terminals 20 to 24 = M

Not applicable

I

th

--

5

• AC-15

--

3

• DC 13 24 V

--

1

• DC 13 110 V

--

0.2

• DC 13 230 V

--

0.1

• Watchdog

Built-in

Built-in

I/O configuration

7

7

ID/ID2 code

0/F

0/F

Assignment of data bits

• Data bit D0

IN1/OUT1

IN1/OUT1

• Data bit D1

IN2/OUT2

IN2/OUT2

• Data bit D2

IN3/OUT3

IN3/OUT3

• Data bit D3

IN4/OUT4

IN4/OUT4

Connection

Spring-loaded terminal connection

Spring-loaded terminal connection

Conductor cross-sections in mm

2

Solid: 2

´ (0.25–1.5)

Finely stranded with end sleeve: 2

´ (0.25–1)

Finely stranded without end sleeve: 2

´ (0.25–1.5)

AWG conductor connections solid or stranded:
AWG 2

´ (24–16)

Solid: 2

´ (0.25–1.5)

Finely stranded with end sleeve: 2

´ (0.25–1)

Finely stranded without end sleeve: 2

´ (0.25–1.5)

AWG conductor connections solid or stranded:
AWG 2

´ (24–16)

Note 1

Disassembly tool for spring-loaded terminal
connection: See "Accessories"

Disassembly tool for spring-loaded terminal
connection: See "Accessories"

Note 2

The module has four floating inputs and four
floating switching outputs. For the input and output
circuits, an external additional supply of 20 to 30 V
according to VDE 0106 (PELV) Safety Class III is
required.

--

Advertising