Siemens IK PI · 2004

6/79

AS-Interface Slaves

I/O modules for operation in IP20 control cabinet

SlimLine

6

Technical specifications (continued)

SlimLine S22.5

4 inputs

4 inputs

4 inputs

new

Screw-type connection

Screw-type connection

Screw-type connection

Standard slave

Standard slave

A/B slave

2-wire

2- and 3-wire

2- and 3-wire

3RK1 200-0CE00-0AA2

3RK1 200-0CE02-0AA2

3RK2 200-0CE02-0AA2

Total current input in mA

£ 50

£ 270

£ 270

Inputs

• Sensor supply via AS-Interface

Short circuit and overload
withstand capability

Short circuit and overload
withstand capability

Short circuit and overload
withstand capability

• Voltage range in V

20 to 30

20 to 30

20 to 30

• Current carrying capacity

for sensor supply in mA

--

200

200

• Connection of sensors

2-wire system

2- and 3-wire system

2- and 3-wire system

• Switching level High in V

³ 10

³ 10

³ 10

• Input current Low/High in mA

£ 1.5 / ³ 5

£ 1.5 / ³ 5

£ 1.5 / ³ 5

I/O configuration

0

0

0

ID/ID2 code

0/F

0/F

A/0

Assignment of data bits

• Data bit D0

IN1

IN1

IN1

• Data bit D1

IN2

IN2

IN2

• Data bit D2

IN3

IN3

IN3

• Data bit D3

IN4

IN4

IN4

Connection

Via screw terminal

Via screw terminal

Via screw terminal

4 inputs

4 inputs

4 inputs

new

Spring-loaded connection

Spring-loaded connection

Spring-loaded connection

Standard slave

Standard slave

A/B slave

2-wire

2- and 3-wire

2- and 3-wire

3RK1 200-0CG00-0AA2

3RK1 200-0CG02-0AA2

3RK2 200-0CG02-0AA2

Total current input in mA

£ 50

£ 270

£ 270

Inputs

• Sensor supply via AS-Interface

Short-circuit and overload
withstand capability

Short-circuit and overload
withstand capability

Short-circuit and overload
withstand capability

• Voltage range in V

20 to 30

20 to 30

20 to 30

• Current carrying capacity

for sensor supply in mA

--

200

200

• Connection of sensors

2-wire system

2- and 3-wire system

2- and 3-wire system

• Switching level High in V

³ 10

³ 10

³ 10

• Input current Low/High in mA

£ 1.5 / ³ 5

£ 1.5 / ³ 5

£ 1.5 / ³ 5

I/O configuration

0

0

0

ID/ID2 code

0/F

0/F

A/0

Assignment of data bits

• Data bit D0

IN1

IN1

IN1

• Data bit D1

IN2

IN2

IN2

• Data bit D2

IN3

IN3

IN3

• Data bit D3

IN4

IN4

IN4

Connection

Spring-loaded terminal connection Spring-loaded terminal connection Spring-loaded terminal connection

Conductor cross-sections in mm

2

Solid: 2

´ (0.25–1.5)

Finely stranded with end sleeve:
2

´ (0.25–1)

Finely stranded without end sleeve:
2

´ (0.25–1.5)

AWG conductor connections solid
or stranded: AWG 2

´ (24–16)

Solid: 2

´ (0.25–1.5)

Finely stranded with end sleeve:
2

´ (0.25–1)

Finely stranded without end sleeve:
2

´ (0.25–1.5)

AWG conductor connections solid
or stranded: AWG 2

´ (24–16)

Solid: 2

´ (0.25–1.5)

Finely stranded with end sleeve:
2

´ (0.25–1)

Finely stranded without end sleeve:
2

´ (0.25–1.5)

AWG conductor connections solid
or stranded: AWG 2

´ (24–16)

Note

Disassembly tool for spring-
loaded terminal connection:
See "Accessories"

Disassembly tool for spring-
loaded terminal connection:
See "Accessories"

Disassembly tool for spring-
loaded terminal connection:
See "Accessories"