Siemens IK PI · 2004

6/53

AS-Interface Slaves

I/O modules for operation in the field

Digital I/O modules IP68 / IP69K - K60R

6

Technical specifications

4 inputs/4 outputs IP68 / IP69K

Standard assignment
3RK1 400–1CR00–0AA3

Slave type

Standard slaves

Operational voltage in accordance
with AS-Interface specification in V

26.5 to 31.6

Total current input in mA

£ 270

Input connection

PNP

Inputs

• Sensor supply via AS-Interface

Short-circuit and overload proof

• Sensors

2- and 3-wire

• Voltage range in V

20 to 30

• Current carrying capacity for all in-

puts
(T

u

£ 40 °C) in mA

200

• Switching level High in V

³ 10

• Input current Low/High in mA

£ 1.5 / ³ 6

• Pin assignments for inputs

PIN 1 = Sensor supply L+
PIN 2 = Data input I
PIN 3 = Sensor supply L-
PIN 4 = Data input I
PIN 5 = Ground connection

Outputs
• Type of output

Electronics

• Current carrying-capacity

DC 12/13 typically
(max. 4 A per module) in A

2

• Maximum summation current

per module in A

4

• Pin assignments for outputs

3 = „-“
4 = Output
5 = Earth connection

• Short-circuit protection

built-in

• Inductive interference protection

built-in

• External voltage supply

DC 24 V

Shared round cable connection
with AS-Interface connection via
M12 socket connector

• Watchdog

built-in

I/O configuration

7

ID/ID2 code

0/F

Assignment of data bits
• Socket 1 (data bit D0)

PIN2/4 = IN1(D0)

• Socket 2 (data bit D1)

PIN2/4 = IN2(D1)

• Socket 3 (data bit D2)

PIN2/4 = IN3(D2)

• Socket 4 (data bit D3)

PIN2/4 = IN4(D3)

• Socket 5 (data bit D0)

PIN4 = OUT1(D0)

• Socket 6 (data bit D1)

PIN4 = OUT2(D1)

• Socket 7 (data bit D2)

PIN4 = OUT3(D2)

• Socket 8 (data bit D3)

PIN4 = OUT4(D3)

4 inputs/4 outputs IP68 / IP69K

Standard assignment
3RK1 400–1CR00–0AA3

AS-Interface certificate

Yes

Approvals

UL, CSA, ship building

Degree of protection

IP68 / IP69K with mounting plate
3RK1 901-0CA00
IP68 test conditions see Section
Overview / Tests IP68 / IP69K
The degree of protection is only
achieved if all M12 connections
are tightened with the correct
torque. I/O sockets which are not
required must be covered with
sealing caps 3RK1 901-1KA00.

Earth connection

PIN5 of each M12 socket is
connected to the grounding plate
in the mounting plate via a pin.

Ambient temperature in °C

-25 to +85

Storage temperature in °C

-40 to +85

Number of I/O sockets

8

Status indications

• I/O indication

Yellow LED

• IndicationU

Help

Green LED

• AS-Interface/diagnostics

indication

Green/red LED

Conductor

via mounting plate for K60
compact module

Note 1

All K60 compact modules are
supplied with stainless steel
screws/sockets

Note 2

To supply the output circuit,
an external supplementary
supply (AUX POWER)
of 20 to 30 V DC is necessary.
The supplementary supply must
comply with VDE 0106 (PELV),
safety class III.