As-interface slaves, I/o modules for operation in the field, Digital i/o modules ip67 - k60 – Siemens ISI EN 50295 User Manual

Page 44

Advertising
background image

Siemens IK PI · 2004

6/44

AS-Interface Slaves

Digital I/O modules IP67 - K60

I/O modules for operation in the field

6

Technical specifications

Technical specifications common to all IP67 – K60 digital I/O modules

Operational voltage in accordance
with AS-Interface specification in V

26.5 to 31.6

Input connection

PNP

Inputs

• Sensor supply via AS-Interface

Short-circuit and overload
withstand capability

• Sensors

2- and 3-wire

• Voltage range in V

20 to 30

• Current carrying capacity f

or all inputs (T

u

£ 40 °C) in mA

200

• Switching level High in V

³ 10

• Input current Low/High in mA

£ 1.5 / ³ 6

Outputs

• Type of output

Electronics

• Short-circuit protection

Built-in

• Inductive interference protection

(free-wheeling diode)

Built-in

• External 24 V DC supply voltage

Over black AS-Interface flat cable

• Watchdog

Built-in

AS-Interface certificate

Available (or under application
in the case of new products)

Approvals

UL, CSA, marine certification
(or under application in the case
of new products)

Degree of protection

IP67

Ground connection

PIN 5 of each M12 socket is
connected with the grounding
sheet in the mounting plate
through a pin

Ambient temperature in °C

-25 to +85

Storage temperature in °C

-40 to +85

Status indications

• I/O display

Yellow LED

• Display U

Aux

Green LED

• AS-Interface/diagnostics display

Green/red LED

Connection

Using mounting plate for K60
compact module

Note 1

All K60 compact modules are
supplied with high-grade steel
screws/sockets

Note 2

To supply the output circuit,
an external supplementary
supply (AUX POWER)
of 20 to 30 V DC is necessary.
The supplementary supply must
comply with VDE 0106 (PELV),
Safety Class III.

8 inputs/2 outputs

8 inputs

8 inputs

new

2 A

--

--

A/B slave

Standard slaves

A/B slaves

Special assignment

Y-II assignment

Y-II assignment

3RK2 400–1HQ00–0AA3

3RK1 200–0DQ00–0AA3

3RK2 200–0DQ00–0AA3

Total current input in mA

£ 300

£ 270

£ 270

Socket assignment, inputs

PIN 1 = Sensor supply L+
PIN 2 = Data input II
PIN 3 = Sensor supply L-
PIN 4 = Data input I
PIN 5 = Earth connection

PIN 1 = Sensor supply L+
PIN 2 = Data input II
PIN 3 = Sensor supply L-
PIN 4 = Data input I
PIN 5 = Earth connection

PIN 1 = Sensor supply L+
PIN 2 = Data input II
PIN 3 = Sensor supply L-
PIN 4 = Data input I
PIN 5 = Earth connection

Outputs

• Current carrying capacity per

output in A DC 12 / DC 13 typ.

2

--

--

• Maximum summation current

per module in A

4

--

--

• Socket assignment, outputs

3 = "-"
4 = Output
5 = Ground connection

--

--

I/O configuration

0 (Addr. 1) / 7 (Addr. 2)

0

0

ID/ID2 code

A/E (Addr. 1 and 2)

1/F

A/E

Assignment of data bits

• Socket 1

PIN4 = IN1(D0) (Addr. 1)
PIN2 = IN2(D1) (Addr. 1)

PIN4 = IN1(D0) (Addr. 1)
PIN2 = IN2(D1) (Addr. 1)

PIN4 = IN1(D0) (Addr. 1)
PIN2 = IN2(D1) (Addr. 1)

• Socket 2

PIN4 = IN2(D1) (Addr. 1)

PIN4 = IN2(D1) (Addr. 1)

PIN4 = IN2(D1) (Addr. 1)

• Socket 3

PIN4 = IN3(D2) (Addr. 1)
PIN2 = IN4(D3) (Addr. 1)

PIN4 = IN3(D2) (Addr. 1)
PIN2 = IN4(D3) (Addr. 1)

PIN4 = IN3(D2) (Addr. 1)
PIN2 = IN4(D3) (Addr. 1)

• Socket 4

PIN4 = IN4(D3) (Addr. 1)

PIN4 = IN4(D3) (Addr. 1)

PIN4 = IN4(D3) (Addr. 1)

• Socket 5

PIN4 = IN1(D0) (Addr. 2)
PIN2 = IN2(D1) (Addr. 2)

PIN4 = IN1(D0) (Addr. 2)
PIN2 = IN2(D1) (Addr. 2)

PIN4 = IN1(D0) (Addr. 2)
PIN2 = IN2(D1) (Addr. 2)

• Socket 6

PIN4 = IN2(D1) (Addr. 2)

PIN4 = IN2(D1) (Addr. 2)

PIN4 = IN2(D1) (Addr. 2)

• Socket 7

PIN4 = OUT1(D0) (Addr. 2)
PIN2 = IN3(D2) (Addr. 2)

PIN4 = IN3(D2) (Addr. 2)
PIN2 = IN4(D3) (Addr. 2)

PIN4 = IN3(D2) (Addr. 2)
PIN2 = IN4(D3) (Addr. 2)

• Socket 8

PIN4 = OUT2(D1) (Addr. 2)
PIN2 = IN4(D3) (Addr. 2)

PIN4 = IN4(D3) (Addr. 2)

PIN4 = IN4(D3) (Addr. 2)

Number of I/O sockets

8

8

8

Note

Module requires two addresses

Module requires two addresses

Module requires two addresses

Advertising