AQUAFORCE Installation, Operation, and Maintenance

8

3.4.4 Analog signals

Shielded cable (#22 AWG, Belden type 8762, Alpha #2411, or equal) should be installed for all D.C. control

wiring. The shield must be terminated in the Controller panel. Do not connect the shield at the other end of the

cable! Insulate the shield so that no electrical connection is made at the other end of the cable. A twisted pair of

#22 AWG conductors (Belden 8442, or equal) can be used in place of shielded cable. The cable length must be

limited to 5,000 feet for #22 AWG wire.

3.4.5 Field connection diagrams

Refer to the pump Installation, Operation, and Maintenance Manual for specific details unique to the pump.
Refer to the flow sensor/transmitter Installation, Operation, and Maintenance manual for specific details unique to the

flow sensor/transmitter.
Job specific wiring and dimensional drawings and typical field connection diagram should be reviewed prior to unit

installation and operation.

3.5 Glossary of terms

VFD

Variable Frequency drive; converts a constant power input into a variable power output for the motor;

a device for controlling motor speed.

Alternation

Process of determining which pump will serve as lead pump and which pump will serve as lag pump.

Destage

To turn off a lag pump.

Lag pump

Standby pump which activates only when lead pump alone cannot efficiently provide sufficient

pressure or flow rate.

Lead pump

Duty pump which runs continuously until a standby pump is required.

LED

Light emitting diode, located on OIP and controller.

OIP

Operator Interface Panel.

PID

Proportional Integral Derivative; 3 variables required for error control.

PV (Process

Signal generated by a sensor which is set up to control the system.

Variable)
Proof timer

Minimum time period before controller acknowledges an input; time period for which a signal must

be stable before it is accepted by the controller as a sustained and valid signal.

RTC

Real time clock.

Stage

To start a lag pump.

SP

Set point.

HD

Hard Deck.

Product Description