Xylem 10 001 262R5 AquaForce Pump Controller User Manual

Page 27

Advertising
background image

AQUAFORCE Installation, Operation, and Maintenance

21

Note:
1. Use the (▲) and (▼) keys to select the appropriate resolution values
2. Use the Next/( ) key and Prev/( ) key to select the desired sign(+ or -) for

VALUE and OFFSET

variables

4.10.5 Exercise menu

Paths: Status Screens / Set up(3) / System(4) / Exercise(3)

See the following table for all

EXERCISE menu items.

Exercise Menu Items

Menu Item

Variable

Default Range Field

Value

Exercise

Period : #Hrs

0

0-999

Amount of time between automatic exercising of the

pumps, in seconds. A value of 0 disables pump exercising

Duration : ###s

0

0-999

Amount of time pumps will be exercised, all pumps

which have not run in the last period will be exercised

simultaneously

Pump exercising will ensure that no pumps go for long periods of time without running. Note that automatic

alternation can also provide this functionality. Pump exercising will only occur when the system is started and in

automatic operation. All pumps which need exercising will exercise on startup.

4.10.6 Alternation menu

Paths: Status Screens / Set up(3) / System(4) / Alternation(4)

The following

ALTERNATION menu options are available:

4.10.7 Timed auto alternation

See the following table for

TIMED AUTO ALTERNATION menu items.

Timed Auto Alternation Menu Items

Menu Item

Variable

Default Range Field

Value

Timed Auto

Period: #Hrs

168

0-999

Alt

Time between pump alternations when using “Timed

Auto Alternation”, in hours. A value of 0 will disable

this function

Duration: ###s

10

0-99

Amount of time that the running pumps will remain on

during alternation, in seconds

Installation