AQUAFORCE Installation, Operation, and Maintenance

15

Installation

4.10 Set up & features

Note: Many sections of the Set up & Features show a path for navigation. An example is shown below to

understand the given path.
Example for system setup path.
Path: Status Screen / Setup(3) / System(4)
To follow the above path press the SETUP/3 key from the system status screen. Then press the ALT/4 key for

number 4 which is a selection number for system and press ENTER key. It will lead to the system setup screen.
Upon powering up the controller, the display will light and show the following screen:

< SEQ 1 >

DIS = ###

SP = ###

SUC = ###

Spd = ###%

STOP MANUAL NORM

Press the

SETUP/3 key once and the following MAIN SET UP menu items will be displayed:

SELECTION: # 0=EXIT
1 = Q-START

4 = SYSTEM

2 = SENSORS

5 = TEST

3 = PUMPS

6 = ALRM/EVT

4.10.0 Sensor Setup

Press the

SET PT/2 key at the Main Set Up menu display. Then press the ENTER key.

The

SENSOR SET UP MENU will be displayed as shown below:

AI 1 TYPE: $$$

SPAN= ### MIN= ##

< OK $ (Y/N) >

To accept the current values, press

YES/7 key and then press the ENTER key.

To set up each field, press the

NO/0 key and then press the ENTER key.

The current

TYPE field starts blinking. Press the up () and down () keys to navigate to the desired TYPE

and then press the

ENTER key to confirm selection.

The following selections are valid:
DIS (Discharge Pressure)
SUC (Suction Pressure)
REDIS (Redundant Discharge Pressure)
NONE
If

REDIS is selected as a desired field, the following screen will get displayed:

ACTIVE SENSOR ##
DRIFT THRESHOLD ##%
DRIFT PR TM ###s
OK $ (Y/N)