4 hand manual operation, 5 setpoint modification – Xylem 10 001 262R5 AquaForce Pump Controller User Manual

Page 43

Advertising
background image

AQUAFORCE Installation, Operation, and Maintenance

37

Operation

5.4 Hand Manual Operation

1. If system is running press the

START/STOP key to stop the system. The solid green LED for start/stop

will turn off and any running pumps will stop.
2. Press the

AUTO/MANUAL key and the screen will display the following:

< >
Manual Speed: #%
STAT1 STAT2 STAT3

3. If the

PUMP LED is not flashing green, enable a pump to run in manual by pressing the

PUMP 1 or PUMP 2 key.

4. Press the

START/STOP key to run the enabled pump(s) in manual. After a brief time delay the

pump(s) starts, and the flashing green LED(s) for pump(s) will turn solid green.
5. Press the

UP () key to increase pump speed to a maximum of 100% of rated speed. Press the

DOWN () key to decrease the speed to 0% where the pump will run at the minimum speed

configured in the VFD, typically 30 HZ.
6. Press the

START/STOP key to stop the system. The running pump(s) will stop.

5.5 Setpoint Modification

To modify the setpoint, press the

SETPT/2 key. The following SET POINT SELECTION screen will be

displayed:
Selection: # 0=Exit
1= Set Point
3= Control Set Point
Use the appropriate numeric key to select the desired menu, then press the

ENTER key. A detailed description

of each menu follows. For example, to select the

SET POINT menu, press the PV/1 key and then press the

ENTER key. The following menu will be displayed:
SP1= ##
Exit: $ (Y/N)
If you agree with the current setpoint settings press the

YES/7 key followed by ENTER. If you would like

to modify the setpoint press the

NO/0 key followed by ENTER at which point the setpoint in the upper left

portion of the screen will begin flashing.
Press the numeric key to modify the setpoint and press

ENTER.

After modifying the set point, press the

YES/7 key to accept the values and return to the SET POINT

SELECTION screen.
To select the

CONTROL SET POINT menu, press the SETUP/3 key and then press the ENTER key. The

following menu will be displayed:
Control Selection: #
1= Set Point
3 = Com Ovrd Exit $(Y/N)
The displayed # value indicates the current active method for set point. To change the active control method,

press the

NO/0 key and then press the ENTER key.

The Control Selection field will start blinking. Change the current value by pressing desired numeric Keys and

then press

ENTER key to confirm. Press the YES/7 key and ENTER key to accept the selection and return to

the

SET POINT SELECTION screen.

Advertising