8 leds, 9 i/o – Xylem 10 001 262R5 AquaForce Pump Controller User Manual

Page 20

Advertising
background image

AQUAFORCE Installation, Operation, and Maintenance

14

Installation

4.8 LEDs

Table 2 gives the meaning of the LED states.
LED Description

START/STOP

On

=

Start

Off = Stop

AUTO/

MANUAL

On

=

Auto

Off = Manual

PUMP

1-4 On

=

Pump

On

Off

=

Pump

Disabled

Blink = Pump Ready, Blink Fast = Pump Failed

RESET/

SILENCE

Off

=

OK

Blink = Reset Required

HELP Off

=

OK

Blink = Event/Alarm(press HELP from the status screens to view)

4.9 I/O

4.9.0 Analog Inputs

The AquaForce Pump Controller is equipped with 2 analog input channels. The analog inputs must provide a

4-20mA signal. Typically, analog inputs will be powered by the 24V power supply within the panel. For analog

inputs which source their own power, consult factory.
Shielded 22 AWG cable should be installed for all analog input wiring. The shield must be terminated in the

AquaForce Pump Controller. Do not connect the shield at the other end of the cable! Insulate the shield so that

no electrical connection is made at the other end of the cable. A twisted pair of #22 AWG conductors can be

used in place of shielded cable. The cable length must be limited to 2,500 feet for #22 AWG wire.

4.9.1 Digital Inputs

The AquaForce Pump Controller is equipped with (3) 24VDC digital input channels. This signal voltage must

be obtained from the 24VDC power supply mounted to the subpanel. It is not recommended that other power

sources be used without factory approval. All digital inputs are automatically assigned based on Table 3. See the

typical wiring diagram in Appendix.

Table 3: Digital Inputs Functionalities

Functionality

DI #

Description

Start/Stop Sw

1

Remote contact can be used to start/stop the system.

Optional DI

2

This digital input can be used as a optional low water switch.

Optional DI

3

This digital input can be used as a push to silence switch.

# 22 AWG cable should be installed for all field wiring to digital inputs.

4.9.2 Digital Output Module

The digital output consists of 1 normally open and 1 normally closed contact for each output rated at 2.5A at

240V. Customer connections are made directly to the terminals mounted on the digital output module. Refer to

section 4.10.13 for relay output setup.