AQUAFORCE Installation, Operation, and Maintenance

19

Installation

STAGE/DESTAGE SETUP MENU ITEMS (continued)

Menu Item

Variable

Default Range Field

Value

PV Destage

Destage: ###%

85

0-100

Enter the percentage of the stabilized speed at which

the lag pump will stop, %.

Destg Pr Timer: ### s

30

0-999

Proof timer prior to stopping lag pump, seconds.

HD Spd: ### %

50

0-100

The lowest speed at which parallel pumps will operate

prior to destaging the lag pump, %. It must be

greater or equal to minimum frequency.

HD Pr Tm: ### s

30

0-999

The proof timer prior to destaging the lag pump when

operating below the HD speed, seconds.

Power Limit

Enable Power Stage

N

Y/N

Stage

Limit $ (Y/N)

Exit: $(Y/N)

Reads motor current entered in pump set up to stage

on next pump after a fixed time delay should current

limit be reached.

4.10.4 VFD menu

Paths: Status Screens / Set up(3) / System(4) / VFD(2)

The first screen has been displayed below:

<Selection:# >

1 = VFD Setup

2 = VFD Set Parameter

3 = VFD Read Parameter

Press the

NEXT ( ) key to go to the next screen.

The display now shows:

<Selection: # >

4 = All DIS SEN Fail