AQUAFORCE Installation, Operation, and Maintenance

29

Installation

4.10.25 Analog input test

Paths: Status Screens / Set up(3) / Test(5) / AI(3)
The Analog Input Test screen is displayed below:
Analog Inputs
1=###%
2=###%
The signal received on the corresponding analog input channel will be indicated in percent next to each input.

4mA = 0%, and 20mA = 100%. Analog inputs 1-2 are 4-20mA inputs. Press

CLEAR key to exit the test.

4.10.26 Analog output test

Paths: Status Screens / Set up(3) / Test(5) / AO(4)

The Analog Output Test screen is displayed below:
Analog Output Test
AO1=###%
OK: $(Y/N)
The signal sent through the corresponding analog output channel will be indicated in percent next to each output.

4mA = 0%, and 20mA = 100%. Analog output is 4-20mA output. Press

CLEAR key to exit the test.

4.10.27 LED test

Paths: Status Screens / Set up(3) / Test(5) / LED(5)
The LED test screen is displayed below:
LED Test
*** SOLID ***
*** OFF ***
*** FLASHING ***
All of the LED’s on the keypad will turn on, off, and then flash. The current status will be displayed on the

screen. The LED test is self terminating.

4.10.28 Key test

Paths: Status Screens / Set up(3) / Test(5) / Key(6)
The

KEY test screen is displayed below:

Key Test
Press a key to test
Press clear to exit
Press any key except for the

CLEAR key, and the display will confirm that the key is working by displaying the

key name. Press

CLEAR key to exit.

4.10.29 Display test

Paths: Status Screens / Set up(3) / Test(5) / Display(7)
The

DISPLAY test screen is shown below:

Press Clear To Exit
< 1 2 3 4 5 6 7 8 9
< 1 2 3 4 5 6 7 8 9
< 1 2 3 4 5 6 7 8 9
The display will show all black characters. Press

CLEAR key to exit the test.