AQUAFORCE Installation, Operation, and Maintenance

40

Maintenance

6. Maintenance

6.1 Preface

The following is a description of the hardware, diagnostics, and corrective action to maintain a process being

controlled by the Pump Controller.
NOTE: THE FOLLOWING SHOULD NOT BE INTERPRETED AS THE MAXIMUM

CONFIGURATION OF THIS CONTROLLER, RATHER THIS DESCRIBES ITS APPLICATION AS AN

AQUAFORCE PUMP CONTROLLER ONLY.

6.2 Technical Overview

The Pump Controller is a microprocessor based dedicated pump controller unique to and exclusively

manufactured by Xylem Goulds Pumps. All aspects of this unit are strictly proprietary to Xylem Goulds Pumps.

6.3 Digital Inputs

The controller has provision for digital inputs with an operating voltage of 24 VDC. This signal voltage must be

obtained from the 24 VDC power supply mounted to the subpanel.
It is not recommended that other power sources be used without factory approval.
Customer connections are made directly to the terminals blocks wired to the digital input module.

6.4 Digital Outputs

The controller has provision for relay outputs to control 240V 50/60 HZ devices.
The relays are not removable. If defective, the digital output module must be returned to the factory for repair.
All relays operate as single pole single throw. Components are provided to reduce contact arc and extend

electrical life.
Customer connections are made directly to the terminals blocks wired to the digital output module.

6.5 Analog Inputs

Analog inputs are provided for process variables and optional transmitters. All analog inputs operate at 4-20mA.

They must be powered from 24 VDC power supply included with the controller

6.6 Memory

The logic is stored in a non-removable flashPROM chip which can only be updated from the

RS-

232 program port on the CPU. The user setup data is stored in non-volatile memory of fixed RAM. While the

controller is powered up, the CPU controller provides the power to save the user values. When the controller is

powered down a 3V lithium ion battery provides the power to store the user’s values. When the battery voltage

drops below 2.5VDC the controller will display *ALARM*. The battery should be replaced as soon as practical

to avoid losing all station settings in the event of a power loss.

6.7 CPU

The CPU does not require any maintenance, and cannot be replaced as a field repair.