AQUAFORCE Installation, Operation, and Maintenance

31

Installation

4.10.33 Low discharge pressure

Paths: Status Screens / Set up(3) / AlrmEvt(6) / Low Discharge(2)

The Low Discharge Pressure menu is displayed below:
Low Dis Press: ##PSI
Low Dis Pr Tm: ##s
Alarm: $ Stop Pumps: $
OK? $ (Y/N)
See following table for all

LOW DISCHARGE PRESSURE menu items.

Low Discharge Pressure Menu Items

Menu Item

Variable

Default Range Field

Value

Low

Low Dis Press: ### PSI

32

0-999

Discharge

The pressure below which an alarm or

Pressure

event will be set, in PSI

Low Dis PrTm: ###s

0

0-999

The proof timer prior to setting an alarm or event, in

seconds. A value of 0 disables this alarm or event.

Alarm: $

N

Y/N

Set this value to “Y” to consider low discharge pressure

an alarm, or set it to “N” to consider it an event.

Stop Pumps: $

N

Y/N

Set this value to “Y” to stop all pumps in the event of

a low pressure alarm or event. Set it to “N” to continue

operation normally during this alarm or event.

4.10.34 High discharge pressure

Paths: Status Screens / Set up(3) / AlrmEvt(6) / High Discharge(3)

The High Discharge Pressure menu is displayed below:
High Dis Press: ##
High Dis Pr Tm: ##s
OK? $ (Y/N)
See following table for all

HIGH DISCHARGE PRESSURE menu items.

High Discharge Pressure Menu Items

Menu Item

Variable

Default Range Field

Value

High

High Dis Press: ### PSI

112

0-999

Discharge

The pressure above which an alarm will be set, in PSI.

Pressure

High Dis Pr Tm: ##s

20

0-999

The proof timer prior to setting an alarm, in seconds,

A value of 0 will disable this alarm.

4.10.35 Low suction pressure

Paths: Status Screens / Set up(3) / AlrmEvt(6) / Low Suction(4)

The Low Suction Pressure menu is displayed below:
Low Suct. Press: ##
Pr Tm: ##s Alarm: $
Auto Rst: $
Reset PSI: ## OK: $ (Y/N)