AQUAFORCE Installation, Operation, and Maintenance

16

Installation

REDIS MENU ITEMS

Menu Item

Variable

Default Range Field

Value

REDIS

Active Sensor : ##

1

1-2

Enter the active discharge pressure sensor number

Drift Threshold: ##%

5

0-100

Pressure difference limit between the active and

redundant pressure sensor in %

Drift Pr Tm : ##s

0

0-999

Proof timer prior to give warning when exceed the

drift threshold limit, in seconds

To set up each field, press the

NO/0 key and then press the ENTER key.

The

ACTIVE SENSOR field will start blinking. Change the current value in Active Sensor field by pressing

desired numeric Keys and then press

ENTER key to confirm.

Press

ENTER key to accept the current DRIFT THRESHOLD value. To change the value in DRIFT

THRESHOLD field, press the desired Numeric Keys and then press ENTER to confirm.
Press

ENTER key to accept the current value of DRIFT PR TM. To change the value in DRIFT PR TM

field press the desired Numeric Keys and then press

ENTER to confirm.

To accept the current values, press

YES/7 key and then press ENTER key. The screen will go back to the

SENSOR SET UP menu displayed above.
Press the

NEXT/( ) key if additional sensors need to be set up. Repeat the above steps for all remaining

sensors.
Pressing

YES/7 key and then the ENTER key at the SENSOR SET UP screen will take the display back to

the

MAIN SET UP screen.

4.10.1 Pump set up

Paths: Status Screens / Set up(3)

Press the

SET UP/3 key at the Main Set Up menu screen. Then press the ENTER key.

The

PUMP SET UP MENU will get displayed as shown below:

SELECTION: # 0= EXIT
1 = NUMBER OF PUMPS
2 = PUMP NAMEPLATE
3 = RESET PUMP TIME
To change the values in

NUMBER OF PUMPS field, press PV/1 key then press the ENTER key. The

following menu will get displayed:

TOTAL PUMPS: #

STANDBY PUMPS: #

OK $ (Y/N)

To set up each field, press the

NO/0 key and ENTER key. Modify the values as desired using the appropriate

numeric key. The pump number is limited to the maximum number of pumps.
To accept the current values, press

YES/7 key and then press ENTER key.

The screen will go back to the

PUMP SET UP MENU display.

To change the values in

PUMP NAMEPLATE field, press SET PT/2 key then press the ENTER key. The

following menu will get displayed:

<PUMP 1

NAMEPLATE>

AMPS:

###.# HP: ###.#

VOLTS:

### Hz: ##

Spd: ####

OK $ (Y/N)