Xylem 10 001 262R5 AquaForce Pump Controller User Manual

Page 28

Advertising
background image

AQUAFORCE Installation, Operation, and Maintenance

22

4.10.8 Alternation basis

See the following table for

ALTERNATION BASIS menu items.

Alternation Basis Menu Items

Menu Item

Variable

Default Range Field

Value

Alternation

1=Pump Sequence

1

1-2

Basis

(The next pump in sequence will become the lead pump

after alternation)

2=Pump Run Time

(The pump with the lowest run time will become the

lead pump after alternation)

4.10.9 PID menu

Paths: Status Screens / Set up(3) / System(4) / PID(5)
See the following table for all

PID menu items.

PID Menu Items

Menu Item

Variable

Default Range Field

Value

PID

PID-P ###

300

0-999

Enter the desired proportional value.

PID-I ###

1

0-999

Enter the desired integral value.

PID-D ###

15

0-999

Enter the desired derivative value.

SP Deviation ###

0

0-999

Enter the value for the number of discharge pressure

units at which a dead band will be created around the

setpoint. The PID will be modified within the dead band

per the index setting below.

Index ###

0

0-999

Enter a value to buffer the response of the PID while

operating in the dead band defined above.

Index = 1 (no impact)

Index = 999 (maximum buffer.)

Start Up ##

5

0-60

Start up delay in seconds

4.10.10 Reset totals menu

Paths: Status Screens / Set up(3) / System(4) / Reset Totals(6)
See the following table for all

RESET TOTALS menu items

Reset Totals Menu Items

Menu Item

Variable

Default Range Field

Value

Reset

RESET TOTAL KW-HRS $

N

Y or N

Totals Press

YES/7 key and ENTER key to reset the total

KW-HRS