AQUAFORCE Installation, Operation, and Maintenance
22
4.10.8 Alternation basis
See the following table for
ALTERNATION BASIS menu items.
Alternation Basis Menu Items
Menu Item
Variable
Default Range Field
Value
Alternation
1=Pump Sequence
1
1-2
Basis
(The next pump in sequence will become the lead pump
after alternation)
2=Pump Run Time
(The pump with the lowest run time will become the
lead pump after alternation)
4.10.9 PID menu
Paths: Status Screens / Set up(3) / System(4) / PID(5)
See the following table for all
PID menu items.
PID Menu Items
Menu Item
Variable
Default Range Field
Value
PID
PID-P ###
300
0-999
Enter the desired proportional value.
PID-I ###
1
0-999
Enter the desired integral value.
PID-D ###
15
0-999
Enter the desired derivative value.
SP Deviation ###
0
0-999
Enter the value for the number of discharge pressure
units at which a dead band will be created around the
setpoint. The PID will be modified within the dead band
per the index setting below.
Index ###
0
0-999
Enter a value to buffer the response of the PID while
operating in the dead band defined above.
Index = 1 (no impact)
Index = 999 (maximum buffer.)
Start Up ##
5
0-60
Start up delay in seconds
4.10.10 Reset totals menu
Paths: Status Screens / Set up(3) / System(4) / Reset Totals(6)
See the following table for all
RESET TOTALS menu items
Reset Totals Menu Items
Menu Item
Variable
Default Range Field
Value
Reset
RESET TOTAL KW-HRS $
N
Y or N
Totals Press
YES/7 key and ENTER key to reset the total
KW-HRS
Installation