AQUAFORCE Installation, Operation, and Maintenance

10

To control variable frequency drives it is necessary to wire RS485 with each VFD.
With certain bypass and control methods it is necessary to disable the adjustable frequency drive from running.

This is accomplished by wiring from the terminals to each VFD’s interlock terminals. Should this wiring be

required, any jumpers which may be found on the VFD’s interlock terminals should be removed.
The control family may be provided with the capability to accept many analog inputs. Typically all analog inputs

must be 4-20mA and powered by the 24VDC power supply in the controller. All shields must be grounded in the

controller only to prevent ground loops and improper signals.
Hardwire communications refers to the capability of the Controller to communicate with an energy management

system. Standard communication features are listed below:
Remote Start/Stop – Remove the jumper from Terminal 200 and install a switch as indicated on the wiring

diagram. CLOSED CONTACT of this switch will provide the start signal.
Remote Alarm Indication – A digital output rated 2.5 AMPs at 240V is supplied. This output closes to indicate

an alarm condition exists.
User Configurable I/O – The Controller comes equipped with the capability to define the operation of any

unused input or output signal. Refer to System Set Up I/O menus.

4.4 Pump package location guidelines

WARNING:

• Assembled units and their components are heavy. Failure to properly lift and support this equipment can

result in serious physical injury and/or equipment damage. Lift equipment only at the specifically identified

lifting points. Lifting devices such as eyebolts, slings, and spreaders must be rated, selected, and used for the

entire load being lifted.

Guideline

Explanation

Make sure that the space around the pump

This facilitates ventilation, inspection,

package is sufficient.

maintenance, and service.

If you require lifting equipment such as hoist or

This makes it easier to properly use the lifting

tackle, make sure that there is enough space above

equipment and safely remove and relocate the

the pump package.

components to a safe location.

Protect the unit from weather and water damage

This is applicable if nothing else is specified.

due to rain, flooding, and freezing temperatures.
Do not install and operate the equipment in closed

Acceptable devices:

systems unless the system is constructed with

• Pressure relief valves

properly-sized safety devices and control devices.

• Compression tanks

• Pressure controls

• Temperature controls

• Flow controls

If the system does not include these devices,

consult the engineer or architect in charge before

you operate the pump.

Take into consideration the occurrence of

The best pump location for noise and vibration

unwanted noise and vibration.

absorption is on a concrete floor with subsoil

underneath.