2 aquaforce modbus communication points – Xylem 10 001 262R5 AquaForce Pump Controller User Manual

Page 58

Advertising
background image

AQUAFORCE Installation, Operation, and Maintenance

52

Appendix

7.2 AquaForce MODBUS Communication Points

Function Points # Point

Range/

Modbus Units

Code

Description

Value

Address

02

1

Pump #1 VFD Failure

1 = Failure

0 = O.K.

10001

02

2

Pump #1 Off Alarm

1 = Alarm

0 = O.K.

10002

02

3

Pump #2 VFD Failure

1 = Failure

0 = O.K.

10003

02

4

Pump #2 Off Alarm

1 = Alarm

0 = O.K.

10004

02

5

Pump #3 VFD Failure

1 = Failure

0 = O.K.

10005

02

6

Pump #3 Off Alarm

1 = Alarm

0 = O.K.

10006

02

7

Pump #4 VFD Failure

1 = Failure

0 = O.K.

10007

02

8

Pump #4 Off Alarm

1 = Alarm

0 = O.K.

10008

02

9

System Reset Required

1 = Yes

0 = No

10009

02

10

Pump #1 Enabled

1 = Enabled 0 = Disabled

10010

02

11

Pump #2 Enabled

1 = Enabled 0 = Disabled

10011

02

12

Pump #3 Enabled

1 = Enabled 0 = Disabled

10012

02

13

Pump #4 Enabled

1 = Enabled 0 = Disabled

10013

02

14

Pump #1 On/Off

1 = On

0 = Off

10014

02

15

Pump #2 On/Off

1 = On

0 = Off

10015

02

16

Pump #3 On/Off

1 = On

0 = Off

10016

02

17

Pump #4 On/Off

1 = On

0 = Off

10017

02

18

System Start/Stop

1 = Start

0 = Stop

10018

02

19

Analog Input #1 Failure

1 = Failure

0 = O.K.

10019

02

20

Analog Input #2 Failure

1 = Failure

0 = O.K.

10020

02

21

General Alarm

1 = Alarm

0 = O.K.

10021

02

22

System Operation Mode

1 = Auto

0 = Manual

10022

05

1

Pump Sequence Alternation

1 = Yes

0 = No

00001

05

2

System Reset Request

1 = Yes

0 = No

00002

05

3

System Start / Stop

1 = Start

0 = Stop

00003

04

1

Discharge Pressure

0 to Span (in AquaForce

30001

PSI

User Setup Menu)

04

2

Suction Pressure

0 to Span (in AquaForce

30002

PSI

User Setup Menu)

04, 06

3

AI #1

0 to Span (in AquaForce

30003,

User Setup Menu)

40003

04, 06

4

AI #2

0 to Span (in AquaForce

30004,

User Setup Menu)

40004

04, 06

5

Setpoint #1

0 to Span (in AquaForce

30005,

User Setup Menu)

40005

04

6

System Power (KW)

0 to Span (in AquaForce

30006

KW

User Setup Menu)

04

7

Drive #1 Current

0 to Span (in AquaForce

30007

A

User Setup Menu)

04

8

Drive #2 Current

0 to Span (in AquaForce

30008

A

User Setup Menu)

04

9

Drive #3 Current

0 to Span (in AquaForce

30009

A

User Setup Menu)