AQUAFORCE Installation, Operation, and Maintenance

24

Password Menu Items (continued)

Menu Item

Variable

Default Range Field

Value

Verify

VERIFY THE PASSWORD

PASSWD >_ _ _ _ _ _<

After entering data in password definition screen this

screen requires the user to confirm the requested

password. If the confirmed number does not agree with

the first number the Enter New Password screen is

repeated to allow the user to get both input screens

to agree.

4.10.13 I/O setup menu

Paths: Status Screens / Set up(3) / System(4) / IO Setup(9)
See the following table for all

I/O Setup menu items.

NOTE: The total available number of I/O to be configured depends on the system setup. Complete all previous

setup screens, specifically pumps and sensors prior to completing the following.

I/O Setup Menu Items

Menu Item

Variable

Default Range Field

Value

DO

Total Avail. DO = #

N/A

0-99

This screen can not be modified. It is here to advise the

user of how many digital outputs can be customized

* DO No: ####

N/A

0-999

Enter the output to be configured as it appears on the

terminal number.

* Code: ###

0

0-255

Enter the code to define the desired functionality of the

output. Valid codes are defined in the Appendix of this

manual.

AO

Total Avail. AO = #

N/A

0-99

This screen can not be modified. It is here to advise the

user of how many analog outputs can be customized

* Code: ###

0

0-255

Enter the code to define the desired functionality of the

output. Valid codes are defined in the Appendix of

this manual.

NOTE: If a programming error happens, an error message is displayed. An error may be due to reprogramming

an input that is currently used by the system or inputting an undefined code number.

4.10.14 Communication Menu

Paths: Status Screens / Set up(3) / System(4) / Communication(10)
The

MODBUS screen is displayed below:

Modbus
9600, 8, 1, 1, N RTU
Node: # Al Ovrd: $
OK: $(Y/N)
The first line confirms setup for Modbus protocol. The second line defines the 9600 bps baud rate, 1 stop bit, 1

start bits, and no parity. The third line requires user input. Obtain the node number from the manufacturer that

supplied the device that will communicate with the Controller.