Xylem 10 001 262R5 AquaForce Pump Controller User Manual

Page 39

Advertising
background image

AQUAFORCE Installation, Operation, and Maintenance

33

Installation

4.10.37 Low water

Paths: Status Screens / Set up(3) / AlrmEvt(6) / LowWater(7)
The Low Water menu is displayed below:
Low Water
Proof Time: ###s
Alarm: $(Y/N)
OK: $ (Y/N)
See following table for all

LOW WATER menu items.

Note: To use the Low Water function connect the low water switch as a optional D1. See the wiring diagram in

Appendix to connect the switch.

Low Water Menu Items

Menu Item

Variable

Default Range Field

Value

Low Water

Proof Time: ###s

0

0-999

The proof time, in seconds prior to setting a low water

alarm or event. A value of 0 in Proof Time variable

disables the Low Water function.

Alarm: $(Y/N)

N

Y/N

Set this value to “Y” to consider Low Water an alarm,

or set it to “N” to consider it an event.

4.10.38 VFD/Comm Failure

Paths: Status Screens / Set up(3) / AlrmEvt(6) / VFD Comm(9)

The

VFD/Comm Failure menu is displayed below:

VFD Proof Time: ###s
VFD COMM Pr Tm: ###s
OK: $(Y/N)
See following table for all

VFD/COMM FAILURE menu items.

VFD/Comm Failure Menu Items

Menu Item

Variable

Default Range Field

Value

VFD

VFD Proof Time: ###s

30

30-999

Comm

The proof timer prior to setting the VFD fail

Failure

alarm, in seconds.

VFD COMM Pr Tm: ###s

30

30-999

The proof timer prior to setting the VFD

communication fail alarm, in seconds.