AQUAFORCE Installation, Operation, and Maintenance

32

Installation

See following table for all

LOW SUCTION PRESSURE menu items.

Low Suction Pressure Menu Items

Menu Item

Variable

Default Range Field

Value

Low

Low Suct Press: ###

5

0-999

Suction

The pressure below which an alarm or event will be

Pressure set.

Pr Tm: ###s

20

0-999

The proof timer prior to setting an alarm or event.

A value of 0 will disable this alarm.

Auto Reset: $

Y

Y/N

Select “Y” to allow this alarm or event to be

automatically reset.

Reset PSI: ###

10

0-999

The pressure at which the controller will

automatically reset when the suction pressure rises

above it.

Alarm: $

N

Y/N

Set this value to “Y” to consider low suction pressure

an alarm, or set it to “N” to consider it an event.

4.10.36 No flow shut down

Paths: Status Screens / Set up(3) / AlrmEvt(6) / NFSD(6)

The

No Flow Shut Down menu is displayed below:

NFSD Tst Pr Tmr ###s
Min Spd . Pr Tmr ##s
Restart PSI Drop ##
Min Run ##m OK $(Y/N)
See following table for all

NO FLOW SHUT DOWN menu items.

No Flow Shut Down Menu Items

Menu Item

Variable

Default Range Field

Value

No Flow

NFSD Tst Pr. Tmr: #s

10

0-999

Shut Down

The No Flow Shut Down test proof timer is the amount

of time, in seconds, the controller will run the system

while the Discharge Pressure is greater then SP.

A value of 0 will disable this alarm.

Min Spd Pr. Tmr #s

30

0-999

The Minimum Speed Proof Timer is the amount of time,

in seconds, the system will run at minimum speed before

shutting off.

Restart PSI Drop ##

10

0-999

The Restart PSI Drop is the value the Discharge Pressure

needs to be less then the SP in order to restart the system.

Min Run: ##m

1

0-999

Minimum Run is the minimum amount of time, in

minutes, that the system will run once it shuts down from

a no flow condition and restarts.