AQUAFORCE Installation, Operation, and Maintenance

28

Installation

See following table for all

DISPLAY menu items.

Display Menu Items

Menu Item

Variable

Default Range Field

Value

Display

Delay to Display Status: ##

3

0-99

The time in minutes after which the fourth line at initial

system status screen will start showing system status if

any key has not been pressed

Status Line Refresh Rate: ##

10

0-99

The time in seconds prior to change the next system

status line

The time in minutes after which the backlight display

60

0-999

will turn off if a key has not been pressed. A value of 0

disables this function

4.10.22 Test set up

Paths: Status Screens / Set up(3) / Test(5)
The

TEST menu screen gets displayed:

Test Selection: #
1=DI 4=AO 7=Disp
2=DO 5=LED 8=Comm
3=AI 6=Key 9=VFD Comm
Press the numeric key corresponding to the desired sub-menu, and then press the

ENTER key.

4.10.23 Digital input test

Paths: Status Screens / Set up(3) / Test(5) / DI(1)
The Digital Input Test screen is displayed below:
Digital Inputs

1

2

3

# # #
Press Clear to Exit
The 0 below each corresponding input will change to a 1 upon receiving a 24VDC digital input on that channel.

Press

CLEAR key to exit the test.

4.10.24 Digital output test

Paths: Status Screens / Set up(3) / Test(5) / DO(2)

The Digital Output Test screen is displayed below:
Digital Outputs

1

2

# #
Enter DO# # (0=Exit)
Press the numeric key corresponding to the digital output for which the state is to be changed, and then press

ENTER to change it. Pressing ENTER multiple times will toggle between 0 and 1. A 1 indicates that the

corresponding relay is closed. When the relay is closed, the corresponding LED on the digital output module will

be lit. Press

0 and ENTER to exit the test.

Note: Any device connected to the relay will be energized.