AQUAFORCE Installation, Operation, and Maintenance

25

Installation

See following table for all

MODBUS menu items.

Modbus Menu Items

Menu Item

Variable

Default Range Field

Value

Modbus

Baud: #####

9600

9600,

The baud rate is user adjustable parameter

19200,

38400

Node: ###

10

0-255

The node number should be supplied by the BMS

communications port.

AI Ovrd: $

N

Y/N

Select “Y” to override analog inputs through the

communications port.

4.10.15 Analog Input Override

If “Y” was entered for “AI Ovrd” in any of the communication setup screens above, the following screen will be

automatically displayed:
AI Override
AI1: $ AI2: $
OK $(Y/N)
Enter a “Y” next to each analog input type that will be overridden through the communications port.

4.10.16 Dynamic Flow Loss Compensation:

This energy savings feature allows user to compensate for the friction losses of system. As flow increases, the

pressure losses due to friction in the system will increase accordingly. This feature will allow controller to modify

the setpoint in real time based on the speed changes to compensate system friction loss. The controller will log

the last 40 real time setpoint changes. Figure 1 shows how this function works with setup parameters using an

example of a three pump system.
Paths: Status Screens / Set up(3) / System(4) / Frict. Loss Comp. (11)
The Friction Loss Compensation screen has been displayed below:
Frict. Loss: ###

>

Auto: $

Enable: $

Log Stab Tmr: ###S
Log Reset: $

OK? $

Press the

YES/7 key to confirm the selection or Press next (►) key to go to the next screen. The display now

shows:
<Total:####

OK? $

Loss1 : ###

Loss4 : ###

Loss2 : ###
Loss3 : ###
Press the Y

ES/7 key to confirm the selection.

Figure 1

Loss1

Loss2

Loss3

H

Q

Setpoint - (Loss1 + Loss2 + Loss3)

Setpoint - (Loss2 + Loss3)

Setpoint - (Loss3)

Setpoint