alarm state, or OK.

Result=(((InputData - Lo_egu)/Span_egu) * 255) + .5.

Write Algorithm Variables

Lo_egu - the low engineering value.
Span_egu - the span of the engineering values.
InputData - the database block's current value.
Result - the value sent to the process hardware.

8BN Signal Conditioning

Description

8-bit binary number.

Input Range

0 - 255.

Scaling

Scales 8-bit binary values to the database block's EGU range. Ignores
the most significant byte.

Read Algorithm

Reads from a 16-bit register using the following algorithm:

Result =((Raw_value/255) * Span_egu) + Lo_egu.

Read Algorithm Variables

Lo_egu - the database block's low engineering value.
Span_egu - the span of the engineering values.
Raw_value - the value stored in the field device's register.
Result - the scaled value stored in the database block.

Write Algorithm

Writes to an 8-bit register using the following algorithm:

Result =(((InputData - Lo_egu)/Span_egu) * 255) + .5.

Write Algorithm Variables

Lo_egu - the low engineering value.
Span_egu - the span of the engineering values.
InputData - the database block's current value.
Result - the value sent to the process hardware.

12AL Signal Conditioning

Description

12-bit binary number.

Input Range

0 - 4095.

Scaling

Scales 12-bit binary values to the database block's EGU range.

Read Algorithm

Reads from a 16-bit register using the same algorithm as 12BN, and
returns a status indicating whether the value is out of range and in an
alarm state, or OK.

Result=((Raw_value/4095) * Span_egu) + Lo_egu.

Read Algorithm Variables

Lo_egu - the database block's low engineering value.
Span_egu - the span of the engineering values.
Raw_value - the value stored in the field device's register.
Result - the scaled value stored in the database block.

Write Algorithm

Writes to a 16-bit register using the same algorithm as 12BN, and
returns a status indicating whether the value is out of range and in an
alarm state, or OK.

Result=(((InputData - Lo_egu)/Span_egu) * 4095) + .5.

Write Algorithm Variables

Lo_egu - the low engineering value.
Span_egu - the span of the engineering values.
InputData - the database block's current value.
Result - the value sent to the process hardware.

12BN Signal Conditioning

Description

12-bit binary number.

Input Range

0 - 4095.

Scaling

Scales 12-bit binary values to the database block's EGU range. Ignores
the most significant nibble (4-bits). Out of range value are treated as
12-bit values. For example, 4096 is treated as 0 because the four