Write Algorithm

Writes to a 16-bit register with alarming using the same algorithm as
15BN, and returns a status indicating whether the value is out of range
and in an alarm state, or OK.

Result=(((InputData - Lo_egu)/Span_egu) * 32767) + .5.

Write Algorithm Variables

Lo_egu - the low engineering value.
Span_egu - the span of the engineering values.
InputData - the database block's current value.
Result - the value sent to the process hardware.

15BN Signal Conditioning

Description

15-bit binary number.

Input Range

0 - 32767.

Scaling

Scales 15-bit binary values to the database block's EGU range. Ignores
the most significant bit.

Read Algorithm

Reads from a 16-bit register using the following algorithm:

Result =((Raw_value/32767) * Span_egu) + Lo_egu.

Read Algorithm Variables

Lo_egu - the database block's low engineering value.
Span_egu - the span of the engineering values.
Raw_value - the value stored in the field device's register.
Result - the scaled value stored in the database block.

Write Algorithm

Writes to a 16-bit register using the following algorithm:

Result =(((InputData - Lo_egu)/Span_egu) * 32767) + .5.

Write Algorithm Variables

Lo_egu - the low engineering value.
Span_egu - the span of the engineering values.
InputData - the database block's current value.
Result - the value sent to the process hardware.

20P Signal Conditioning

Description

6400 – 32000 Clamp.

Input Range

6400 – 32000.

Scaling

Scales binary values to the database block's EGU range. Clamps value
to 6400 – 32000 range.

Read Algorithm

Reads from a 16-bit register using the following algorithm:

Result =(((Raw_value - 6400)/25600) * Span_egu) + Lo_egu.

Read Algorithm Variables

Lo_egu - the database block's low engineering value.
Span_egu - the span of the engineering values.
Raw_value - the value stored in the field device's register.
Result - the scaled value stored in the database block.

Write Algorithm

Writes to a 16-bit register using the following algorithm:

Result =(((InputData - Lo_egu)/Span_egu) * 25600) + 6400.5.

Write Algorithm Variables

Lo_egu - the low engineering value.
Span_egu - the span of the engineering values.
InputData - the database block's current value.
Result - the value sent to the process hardware.

TNON Signal Conditioning

Description

0 – 32000 Clamp.

Input Range

0 – 32000.

Scaling

Scales binary values to the database block's EGU range. Clamps value
to 0 – 32000 range.

Read Algorithm

Reads from a 16-bit register using the following algorithm: