14AL Signal Conditioning

Description

14-bit binary number.

Input Range

0 - 16383.

Scaling

Scales 14-bit binary values to the database block's EGU range.

Read Algorithm

Reads from a 16-bit register using the same algorithm as 14BN, and
returns a status indicating whether the value is out of range and in an
alarm state, or OK.

Result=((Raw_value/16383) * Span_egu) + Lo_egu.

Read Algorithm Variables

Lo_egu - the database block's low engineering value.
Span_egu - the span of the engineering values.
Raw_value - the value stored in the field device's register.
Result - the scaled value stored in the database block.

Write Algorithm

Writes to a 16-bit register using the same algorithm as 14BN, and
returns a status indicating whether the value is out of range and in an
alarm state, or OK.

Result=(((InputData - Lo_egu)/Span_egu) * 16383) + .5.

Write Algorithm Variables

Lo_egu - the low engineering value.
Span_egu - the span of the engineering values.
InputData - the database block's current value.
Result - the value sent to the process hardware.

14BN Signal Conditioning

Description

14-bit binary number.

Input Range

0 - 16383.

Scaling

Scales 14-bit binary values to the database block's EGU range. Ignores
the most significant 2 bits.

Read Algorithm

Reads from a 16-bit register using the following algorithm:

Result=((Raw_value/16383) * Span_egu) + Lo_egu.

Read Algorithm Variables

Lo_egu - the database block's low engineering value.
Span_egu - the span of the engineering values.
Raw_value - the value stored in the field device's register.
Result - the scaled value stored in the database block.

Write Algorithm

Writes to a 16-bit register using the following algorithm:

Result=(((InputData - Lo_egu)/Span_egu) * 16383) + .5.

Write Algorithm Variables

Lo_egu - the low engineering value.
Span_egu - the span of the engineering values.
InputData - the database block's current value.
Result - the value sent to the process hardware.

15AL Signal Conditioning

Description

15-bit binary number.

Input Range

0 - 32767.

Scaling

Scales 15-bit binary values to the database block's EGU range.

Read Algorithm

Reads from a 16-bit register with alarming using the same algorithm
as 15BN, and returns a status indicating whether the value is out of
range and in an alarm state, or OK.

Result=((Raw_value/32767) * Span_egu) + Lo_egu.

Read Algorithm Variables

Lo_egu - the database block's low engineering value.
Span_egu - the span of the engineering values.
Raw_value - the value stored in the field device's register.
Result - the scaled value stored in the database block.

Advertising