4-10

4. WIRING

Status Output / Alarm Output

IMPORTANT

Since this is an isolated transistor output, be
careful of voltage and polarity when wiring.
Do not apply a voltage larger than 30V DC or a
current larger than 0.2A in order to prevent
damage to the instrument.
This output cannot switch an AC load. To switch
an AC load, an intermediate relay must be
inserted as shown in Figure 4.4.13 or Figure
4.4.14.
*The alarm output operates from closed (normal)
to open (alarm occurrence) in the default value
(as setup upon plant shipment). Changes can
be made via the parameter settings.

F0421.EPS

Load

Load

Protective diode

Protective
diode

External power supply
30V DC, 0.2A. max

AXFA11

External power supply
30V DC, 0.2A. max

AXFA11

This connection is not possible.

This connection is not possible.

SO1

+

SO2

+

COM

SO1

+

SO2

+

COM

Electromagnetic

valve

Electromagnetic

valve

AC power supply

Relay

Figure 4.4.13 Status Output Connection

F0422.EPS

Load

Protective diode

External power supply
30V DC, 0.2A. max

AXFA11

AXFA11

This connection is not possible.

AL

+

AL

-

AL

+

AL

-

Electromagnetic

valve

AC power supply

Relay

Figure 4.4.14 Alarm Output Connection