4) menu e: pulse setting items, 4) menu e: pulse setting items -19 – Yokogawa ADMAG AXF User Manual

Page 48

Advertising
background image

IM 01E20C01-01E

6-19

6. PARAMETER DESCRIPTION

and “dl” is set for D31: Ttl User
Unit
.
“dl” is indicated for the totalized
units in the Display Mode and is
counted in 1 dl steps.

(4) Menu E: Pulse Setting items

Menu E contains items relevant to pulse output.

[E10: Pulse Unit] Setting of the pulse units
→ Refer to the description of parameter B32: Pulse
Unit

[E11: Pulse Scale] Setting of the pulse scale
→ Refer to the description of parameter B33: Pulse
Scale

[E12: Pulse Width] Setting of the pulse width
This parameter selects the pulse width (i.e., ms :
millisecond) that is output.

Data Range

T0621.EPS

Setting

Pulse Rate (pps)

Maximum Value

Minimum Value

(1) 0.05ms

(2) 0.1ms

(3) 0.5ms

(4) 1ms

(5) 20ms

(6) 33ms

(7) 50ms

(8) 100ms

(0) 50% Duty

10000

5000

1000

500

25

15

10

5

11000

0.0001

(pps: pulses per second)

NOTE

*:The pulse width with the exception of “50%

Duty” is the “Closed (On)” time for each pulse
in case that “Closed (On) Act” is sellected for
E20: Pulse Active Mode.

F0603.EPS

Pulse width

Closed(On)

Open(Off)

A limit applies to the maximum pulse scale that
can be set with respect to the pulse width. If a
value in excess of this limit is set, a setting
alarm will be displayed.

[E13: Pulse Low Cut] Setting of the pulse output
stop range
This parameter allows the settings to be made which
prevent pulse output when the flow rate is at or below
the low-cut setting value. In cases where there are
multiple ranges or forward/reverse ranges, low cut is
carried out at the setting value for the smallest span
(i.e., an integer between 0 and 10%).
Example: When the first range = 10 m

3

/h, the second

range = 100 m

3

/h, and the Pulse Low Cut =

3%, no pulse output is carried out at flow
rates of 0.3 m

3

/h or lower.

[E20: Pulse Active Mode] Setting of active mode
for pulse output
This parameter sets whether pulse-output active mode
is to be “On Active” or “Off Active”.

Item

Description

T0622.EPS

Open (Off) Act

Closed (On) Act

When pulse output is carried out, contacts

are Open (Off).

When pulse output is carried out, contacts

are Closed (On).

Example: When E12: Pulse Width is 1 ms, output

takes place as follows in accordance with the
setting for E20: Pulse Active Mode.

F0604.EPS

1 ms

1 ms

Closed (On) Active

Open (Off) Active

Closed(On)

Open(Off)

Advertising