7. OPERATION VIA BRAIN TERMINAL (BT200)

7.2 AXFA11 Operation

Using a BT200

This section describes procedures for setting parameters
using a BRAIN Terminal (BT200). For more details
regarding AXFA11 functions, refer to Chapter 6:
Parameter Description; and for more details regarding
BT200 operation methods, refer to the BT200 User’s
Manual (IM 01C00A11-01E).

7.2.1

BT200 Connection

Connection to a 4 to 20 mA DC signal line

The communication signal of the AXFA11 is superim-
posed onto the 4 to 20mA DC analog signals to be
transmitted.

AXFA11 terminals

BT200

BT200

BT200

Relaying
terminals

4 to 20mA
DC signal
transmission
line

Control room

Receiving
resistance:
250 to 450

Receiving
instrument

Terminal
board

F0705.EPS

I

I

Figure 7.2

Connecting the BT200

WARNING

Be sure to set parameters as "Protect" on the
write protect function after finish of parameter
setting work.
Under extremely rare case, the infra-red switches
may respond unexpectedly in such conditions as
sticking ball of water or extraneous substances on
the surface of display panel glass according to
the principle of infra-red switch operation.
Its probability rises in such cases as sticking rain
water by storm or other similar situation and
washing up work near flowmeter installation place.
Either to illuminate or stop illuminating the infra-
red switches by the flashlight may cause the
mis-reaction.
Refer to Chapter 6 "Menu P: Parameter Protec-
tion Items" and section "10.2.3" how to use the
write protect function in detail.

IMPORTANT

Restrictions exist with regard to the distance
over which communication is possible. (See
Chapter 11: Outline.)

IMPORTANT

If the power of flowmeter is turned off within 30
seconds after parameters have been set, these
settings will be canceled. Accordingly, please
keep the power on for at least 30 seconds after
setting parameters.

IMPORTANT

After approximately 5 minutes of inactivity, the
Auto Power-Off function will operate to turn your
BT200 off.

NOTE

In case of BT200, the parameters are displayed
in English only.
Even if the language with the exception of English
is selected at B10/H30: Language, the param-
eters are displayed in English upon BT200.

7.2.2

The data update and upload/
download function of BT200

(1) The data update of BT200

When the following parameters are displayed, the mea-
sured data is updated automatically every seven seconds.

T0703.EPS

Item

A10

A20

A21

A30

A31

A32

C44

G22

G40

G41

G42

Name (BRAIN)

FLOW RATE (%)

FLOW RATE

FLW RATE (mA)

TOTAL

REV TOTAL

DIF TOTAL

VELOCITY CHK

4-20 BURNOUT

OPERATE TIME

ALM RECORD1

ALM TIME 1

Item

G43

G44

G45

G46

G47

G48

N23

N24

P20

P23

Name (BRAIN)

ALM RECORD2

ALM TIME 2

ALM RECORD3

ALM TIME 3

ALM RECORD4

ALM TIME 4

TEST SI1

TEST SI2

W PROTECT

SOFT SEAL