6-8

6. PARAMETER DESCRIPTION

T0608-2.EPS

Item

Name

Display unit

(BRAIN)

Data range

Display unit

/BRAIN

Default value

(*): Indicated item

Units

R/W

Position

of decimal

point

Description

G14 H/L Alarm Hys

(H/L ALM HYS)

W

%

0

0 to 10

5 %

Sets hysteresis width for high-low
flow rate limit alarm

G20 Alm Out Act Mode

(ALM OUT ACT)

W

Closed(On) Act
Open(Off) Act

Open(Off)
Act

Selects whether alarm output will
be set to “On Active” or “Off Active.”

G22 4-20mA Burn Out

(4-20 BURNOUT)

R

High
Low

Displays the current output
during a CPU failure.

G30 Alm-Setting

(ALM-SETTING)

W

No
Yes

Yes

Selects whether a setting alarm is
to be specified as an alarm.

G31 Alm-Sig Over

(ALM-SIG OVER)

W

No
Yes

Yes

Selects whether a signal overflow
alarm is to be specified as an alarm.

G32 Alm-Emp Pipe

(ALM-EMP PIPE)

W

No
Yes

Yes

Selects whether an empty pipe alarm
is to be specified as an alarm.

G33 Alm-HH/LL

(ALM-HH/LL)

W

No
Yes

No

Selects whether a flow rate
high-high or low-low alarm is
to be specified as an alarm.

G34 Alm-Adhesion

(ALM-ADHESION)

W

No
Yes

No

Selects whether an electrode adhesion
alarm is to be specified as an alarm.

G40 Operation Time

(OPERATE TIME)

R

0D 00:00 to
99999D 23:59

Operation time

G42 Alm Record Time1

(ALM TIME 1)

R

0D 00:00 to
99999D 23:59

Displays the operation time at the
occurrence of the most recent alarm.

G43 Alm Record2

(ALM RECORD2)

R

Same as G41
(Alm Record 1)

Displays the content of the second
most recent alarm.

G44 Alm Record Time2

(ALM TIME 2)

R

0D 00:00 to
99999D 23:59

Displays the operation time at occurrence
of the second most recent alarm.

G45 Alm Record3

(ALM RECORD3)

R

Same as G41
(Alm Record 1)

Displays the content of the third most
recent alarm.

G46 Alm Record Time3

(ALM TIME 3)

R

0D 00:00 to
99999D 23:59

Displays the operation time at the
occurrence of the third most recent alarm.

G47 Alm Record4

(ALM RECORD4)

R

Same as G41
(Alm Record 1)

Displays the content of the fourth
most recent alarm.

G48 Alm Record Time4

(ALM TIME 4)

R

0D 00:00 to
99999D 23:59

Displays the operation time at the
occurrence of the fourth most recent alarm.

G60 —

(SELF CHECK)

R

Good
Error

See “6.5 Alarm Functions”.

G21 4-20mA Alarm Out

(4-20 ALM OUT)

W

2.4mA or Less
4.0mA
Hold
21.6mA or More

21.6mA or
More

Selects the current output during
alarm occurrence.

G41 Alm Record1

(ALM RECORD1)

R

10:uP Fault
11:EEPROM Fault
12:A/D(H) Fault
13:A/D(L) Fault
14:A/D(Z) Fault
15:Coil Open
16:EEPROM Dflt
18:Power Off
19:Inst Pwr Fail
28:WDT
30:Sig Overflow
31:Empty Pipe
33:Adhesion Alm

Displays the content of the most
recent alarm.