Yokogawa ADMAG AXF User Manual

Page 39

Advertising
background image

IM 01E20C01-01E

6-10

6. PARAMETER DESCRIPTION

T0610-2.EPS

Item

Name

Display unit

(BRAIN)

Data range

Display unit

/BRAIN

Default value

(*): Indicated item

Units

R/W

Position

of decimal

point

Description

J30 Power Synch

(POWER SYNCH)

W

No
Yes

Yes

Selects whether or not the internal
frequency is to be synchronized
with the power supply frequency.

J40 Memo 1

(MEMO 1)

W

ASCII 16 characters

Memo field

J41 Memo 2

(MEMO 2)

W

ASCII 16 characters

Memo field

J42 Memo 3

(MEMO 3)

W

ASCII 16 characters

Memo field

J50 Software Rev No

(SOFTWARE REV)

R

Software revision number

J60 —

(SELF CHECK)

R

Good
Error

See “6.5 Alarm Functions”.

J31 Power Frequency

(POWER FREQ)

R/W

Hz

47.00 to 63.00

2

50.00

Displays the power-supply
frequency (for Power Synch =
“Yes”), or sets the power-supply
frequency (for Power Synch=“No”).

(10) Item K (Menu K): Diagnostic Function Setting items

Menu K contains items that are relevant to the diagnosis of insulation adhesion to the electrode.

T0611.EPS

Item

Name

Display unit

(BRAIN)

Data range

Display unit

/BRAIN

Default value

(*): Indicated item

Units

R/W

Position

of decimal

point

Description

K60 —

(SELF CHECK)

R

Good
Error

See “6.5 Alarm Functions”.

K00 Diagnosis

(DIAGNOSIS)

K10 Adhesion Check

(ADHESION CHK)

W

No
Yes

No

Selects whether or not to perform diagnosis
of adhesion to the electrode.

K11 Adhesion Level1

(ADH LEVEL1)

W

M ohm

0.00 to 100.00

2

0.10

Sets the resistance value for adhesion
Level 1 to the electorode.

K12 Adhesion Level2

(ADH LEVEL2)

W

M ohm

0.00 to 100.00

2

0.50

Sets the resistance value for adhesion
Level 2 to the electorode.

K13 Adhesion Level3

(ADH LEVEL3)

W

M ohm

0.00 to 100.00

2

1.00

Sets the resistance value for adhesion
Level 3 to the electorode.

K14 Adhesion Level4

(ADH LEVEL4)

W

M ohm

0.00 to 100.00

2

3.00

Sets the resistance value for adhesion
Level 4 to the electorode.

K15 Adh Measure Value

(ADH MEAS VAL)

R

M ohm

2

Displays the resistance value for
adhesion to the electrode.

(11) Item M (Menu M): Automatic Zero-Adjustment Function Setting items

Menu M contains items that are relevant to automatic zero adjustment.

Item

Name

Display unit

(BRAIN)

Data range

Display unit

/BRAIN

Default value

(*): Indicated item

Units

R/W

Position

of decimal

point

Description

T0612.EPS

M60 —

(SELF CHECK)

R

Good
Error

See “6.5 Alarm Functions”.

M11 Magflow Zero

(MAGFLOW ZERO)

M00 Adjustment

(ADJUSTMENT)

R/W

-99.999 to 99.999

3

0.000

Displays the result of the automatic
zero adjustment, or sets the zero point.

M10 Auto Zero Exe

(AUTOZERO EXE)

W

No Execution
Execution

No Execution

Selects whether or not automatic
zero adjustment is carried out.
Linked with B50.