<2. Handling Cautions>

2-7

IM 01C27B01-01EN

(2) Operation

WARNING

Take care not to generate mechanical sparking

when access to the instrument and peripheral

devices in a hazardous location.

(3) Maintenance and repair

WARNING

The instrument modification or parts replacement

by other than an authorized Representative of

Yokogawa Electric Corporation is prohibited and

will void the certification.

(4) Name Plate

• Name Plate

: Refer to USER'S MANUAL.

Made in Japan

TOKYO 180-8750 JAPAN

MODEL

SUFFIX

SUPPLY

OUTPUT

MWP

mA DC

V DC

STYLE

CAL

RNG

NO.

F0207.ai

• Tag plate for intrinsically safe type

F0208.ai

KS27

No. KEMA 10ATEX0164 X

Ex ia IIC T4 Ga

ENCLOSURE: IP66/IP67

Tamb.: -50 TO 70°C

MAX PROCESS TEMP.: 120°C

*3

POTENTIAL ELECTROSTATIC CHARGING HAZARD - SECURE DISTANCE

OF 100MM FROM ANTENNA.

USE ONLY BATTERY PACK YOKOGAWA F9915MA OR F9915NS.

POTENTIAL ELECTROSTATIC CHARGING HAZARD - SEE USER'S MANUAL.

WARNING

MODEL: Specified model code.

STYLE: Style code.

SUFFIX: Specified suffix code.

SUPPLY: Supply voltage.

OUTPUT: Output signal.

MWP: Maximum working pressure.

CAL RNG: Specified calibration range.

NO.: Serial number and year of production

*1

.

TOKYO 180-8750 JAPAN:

The manufacturer name and the address

*2

.

*1:

The first digit in the final three numbers of the serial

number appearing after “NO.” on the nameplate indicates

the year of production. The following is an example of a

serial number for a product that was produced in 2010:

91K819857 032

The year 2010

*2:

“180-8750” is a zip code which represents the following

address.

2-9-32 Nakacho, Musashino-shi, Tokyo Japan

*3: The identification number of Notified Body.

2.8.4 IECEx Certification

Caution for IECEx Intrinsically safe type.
Note 1. Model EJX Series pressure transmitters

with optional code /SS27 for potentially

explosive atmospheres:

• No. IECEx KEM 10.0074X

• Applicable Standard:

IEC 60079-0:2011, IEC 60079-11:2011,

IEC 60079-26:2006

• Type of Protection and Marking code:

Ex ia IIC T4 Ga

• Ambient Temperature: –50°C to 70°C

• Process Temperature (Tp.): 120°C max.

• Enclosure: IP66/IP67

Note 2. Installation

• Installation should be in accordance with

local installation requirements.

(Refer to the Control Drawing)

Amplifier housing code 7

Hazardous Area

[Control Drawing]

F0209.ai

Amplifier housing code 8 and 9

Hazardous Area

*1: These apparatus are simple apparatus.

*2: Arrester may not be connected.

Transmitter

Battery Pack

Transmitter

Battery Pack

Arrester

(*1, *2)

Antenna

(*1)

Antenna connector

Note 3. Maintenance and Repair

• The instrument modification or parts

replacement by other than authorized

representative of Yokogawa Electric

Corporation is prohibited and will void IECEx

Intrinsically safe Certification.

WARNING

The instrument modification or parts replacement

by other than an authorized Representative of

Yokogawa Electric Corporation is prohibited and

will void the certification.