2 routing the impulse piping, Routing the impulse piping -3, Important – Yokogawa EJX430B User Manual

Page 27

Advertising
background image

<5. Installing Impulse Piping>

5-3

IM 01C27B01-01EN

5.1.2 Routing the Impulse Piping

(1) Process Pressure Tap Angles
If condensate, gas, sediment or other extraneous

material in the process piping gets into the impulse

piping, pressure measurement errors may result. To

prevent such problems, the process pressure taps

must be angled as shown in figure 5.4 according to

the kind of fluid being measured.

NOTE

• If the process fluid is a gas, the taps must be

vertical or within 45° either side of vertical.

• If the process fluid is a liquid, the taps must

be horizontal or below horizontal, but not

more than 45° below horizontal.

• If the process fluid is steam or other

condensing vapor, the taps must be

horizontal or above horizontal, but not more

than 45° above horizontal.

[Gas]

Pressure

taps

Process

piping

[Steam]

[Liquid]

45°

45°

45°

45°

45°

45°

F0504.ai

Figure 5.4

Process Pressure Tap Angle

(For Horizontal Piping)

(2) Position of Process Pressure Taps and

Transmitter

If condensate (or gas) accumulates in the impulse

piping, it should be removed periodically by

opening the drain (or vent) plugs. However, this will

generate a transient disturbance in the pressure

measurement, and therefore it is necessary to

position the taps and route the impulse piping so

that any extraneous liquid or gas generated in the

leadlines returns naturally to the process piping.

• If the process fluid is a gas, then as a rule the

transmitter must be located higher than the

process pressure taps.

• If the process fluid is a liquid or steam, then as a

rule the transmitter must be located lower than

the process pressure taps.

(3) Impulse Piping Slope
The impulse piping must be routed with only an

upward or downward slope. Even for horizontal

routing, the impulse piping should have a slope of

at least 1/10 to prevent condensate (or gases) from

accumulating in the pipes.

(4) Temperature Difference Between Impulse

Lines (for differential pressure transmitters)

If there is a temperature difference between the

high and low impulse lines, the density difference

of the fluids in the two lines will cause an error in

the measurement pressure. When measuring flow,

impulse lines must be routed together so that there

is no temperature difference between them.

(5) Condensate Pots for Steam Flow

Measurement (for differential pressure

transmitters)

If the liquid in the impulse piping repeatedly

condenses or vaporizes as a result of changes

in the ambient or process temperature, this will

cause a difference in the fluid head between the

high pressure and low pressure sides. To prevent

measurement errors due to these head differences,

condensate pots are used when measuring steam

flow.

(6) Preventing Wind Speed Effects in Very Low

Differential Pressure Measurement

(for differential pressure transmitters)

IMPORTANT

When using a differential pressure transmitter

to measure very low pressures (draft pressure),

the low pressure connection port is left open

to atmospheric pressure (the reference

pressure). Any wind around the differential

pressure transmitter will therefore cause errors

in the measurement. To prevent this, it will be

necessary either to enclose the transmitter in

a box, or to connect an impulse line to the low

pressure side and insert its end into a wind-

excluding pot (cylindrical with a base plate).

(7) Preventing Freezing
If there is any risk that the process fluid in the

impulse piping or transmitter could freeze, use a

steam jacket or heater to maintain the temperature

of the fluid.

Advertising
This manual is related to the following products: