<9. Maintenance>

9-10

IM 01C27B01-01EN

Connect the device configuration tool and check self-diagnostics.

Does the self-

diagnostic indicate problem

location?

Contact Yokogawa service personnel.

F0909.ai

Are valves opened or

closed correctly?

Refer to Alarm Message Summary in

Subsection 9.5.3.

YES

NO

Refer to individual model user manuals

and connect piping as appropriate for

the measurement purpose.

Fix pressure leaks, paying particular

attention to connections for impulse

piping, pressure-detector section, etc.

Fully close equalizing valve, and fully

open high pressure and low pressure

valves.

NO

YES

YES

NO

YES

Adjust the zero point.

NO

NO

YES

Is there any pressure leak?

Is impulse piping

to high pressure and low

pressure side correct?

Is zero point

adjusted correctly?

Output travels beyond 0% or 100%.

Connect the device configuration tool and check self-diagnostics.

Contact Yokogawa service personnel.

F0910.ai

Are valves opened or

closed correctly?

Is impulse piping

connected correctly?

Refer to Alarm Message Summary in

Subsection 9.5.3.

Provide lagging and/or cooling, or allow

adequate ventilation.

Refer to Section 9.2 "Calibration

Instruments Selection".

Fully close equalizing valve, and fully

open high pressure and low pressure

valves.

Refer to individual model user manuals

and connect piping as appropriate for

the measurement purpose.

Adjust the output.

Is transmitter

installed where there is

marked variation in

temperature?

Is output adjusted correctly?

Large output error.

Does the self-

diagnostic indicate problem

location?

Were appropriate

instruments used for

calibration?

YES

NO

YES

NO

NO

YES

NO

YES

NO

YES

NO

YES