<8. Setting Parameters>

8-22

IM 01C27B01-01EN

c. Using External Zero-adjustment Screw
External Zero-adjustment parameter (External

Zero Trim) can set permission or prohibition to

adjustment by External Zero-adjustment Screw.
Set “Trim on” to use the External Zero-adjustment

Screw. (“Trim on” at shipment)
Use a slotted screwdriver to turn the zero-

adjustment screw. Equalize the transmitter, then

turn the screw clockwise to increase the output or

counterclockwise to decrease the output. The zero

point adjustment can be made with a resolution

of 0.01% of the setting range. The degree of zero

adjustments varies with the screw turning speed;

turn the screw slowly to make a fine adjustment,

quickly to make a rough adjustment.

Zero-adjustment Screw

F0807.ai

Figure 8.5

Zero-adjustment Screw

(2) Span Adjustment
Span Adjustment is function to change the input and

output characteristic that assumed the bottom value

(zero point) of measurement range a standard.

Therefore, perform span adjustment (adjustment

of the upper limit value) after zero adjustment

(adjustment of bottom limit value).
After adding the pressure at point of adjustment and

setting pressure value as parameter, the transmitter

calculates quantity of adjustment and performs

adjustment automatically.

• Procedure to call up the lower limit value

parameter (Calibration Lowest Point).

AI1 block: Calibration Lowest Point
Set the lower limit adjustment value on the

differential pressure/pressure (AI1 block)

Calibration Lowest Point parameter screen.

Apply a reference pressure corresponding to

the lower limit of the measurement range to

the differential pressure/pressure transmitter

and confirm the reference pressure when it has

stabilized.

• Procedure to call up the calibration adjustment

parameter (Cal Cmd).

AI1 block: Cal Cmd: CAL_LOW
Confirm the lower limit of the measurement

range in CAL_LOW of the differential pressure

(AI1 block) Cal Cmd parameter.

• Procedure to call up the calibration status

parameter (Cal Status).

AI1 block: Cal Status
Confirm the calibration status of CAL_

SUCCESS(1) using the Cal Status parameter.

• Procedure to call up the upper limit adjustment

parameter (Calibration Highest Point).

AI1 block: Calibration Highest Point
Set the upper limit adjustment value for the

differential pressure (AI1 block) Calibration

Highest Point parameter. Apply a reference

pressure corresponding to the upper limit of the

measurement range to the differential pressure/

pressure transmitter and confirm the reference

pressure when it has stabilized.

• Procedure to call up the calibration adjustment

parameter (Cal Cmd).

AI1 block: Cal Cmd: CAL_HIGH
Confirm the upper limit of the measurement

range in CAL_HIGH of the differential pressure/

pressure (AI1 block) Cal Cmd parameter.

• Procedure to call up the calibration status

parameter (Cal Status).

AI1 block: Cal Status
Confirm the calibration status of CAL_

SUCCESS(1) using the Cal Status parameter.

(3) Adjustments for Static Pressure
For the EJX differential transmitters, zero point and

span adjustments of static pressure is performed in

the same way as with the primary process variable

(PV).

Adjustment should be performed using the static

pressure (AI2 block) Cal Cmd parameter. After

calibration, confirm the status by using the static

pressure (AI2 block) Cal Status.

• Procedure to call up the calibration adjustment

parameter (Cal Cmd).

AI2 block: Cal Cmd

Perform differential pressure zero/span adjustment

before static pressure zero/span adjustment.