8.3.14 Zero Point Adjustment and Span

Adjustment

Each EJX-B Series Differential Pressure/Pressure

Transmitter is characterized by factory. But there

are some errors caused by environment and

installed posture.
There are Zero and Span Adjustments to fine-tune

those errors.

Zero Adjustment is adjustment for one point to

adjust the bottom value of the measurement range

as 0 % of output.

.

The Span Adjustment defines input and output

characteristic between two points that’s one side

assumed as standard.

This is used when there is doubt of span drift or

when it is impossible to make zero at absolute

pressure with adjustment for user’s pressure

standard.
(1) Zero Point Adjustment

a. To set 0% at current input, perform

following procedure.

This method is used only when the pressure at

bottom of measurement range is zero.

• Procedure to call up the lower limit adjustment

parameter (Calibration Lowest Point).

AI1 block: Calibration Lowest Point
Set 0 to Calibration Lowest Point parameter for

differential pressure (Al1 block).

• Procedure to call up the calibration adjustment

parameter (Cal Cmd).

AI1 block: Cal Cmd : CAL_LOW
Lower limit is changed by using Cal Cmd

parameter for differential pressure/pressure

(Al1 block).

• Procedure to call up the calibration status

parameter (Cal Status).

AI1 block: Cal Status
Confirm the calibration status of CAL_

SUCCESS(1) using the Cal Status parameter.

b. To match current input and output value,

follow procedure

Like tank level measurement that is impossible to

set actual level to zero, output value is adjustment

to actual level by other measurement using

glassgage.

Example:

Differential Pressure and Pressure

Transmitter’s span is 0 to 25.00kPa, current

level is 13.50kPa, current output is 13.83kPa.

• Procedure to call up the lower limit adjustment

parameter (Calibration Lowest Point).

AI1 block : Calibration Lowest Point

.

Set the actual level value of 13.50 kPa to the

Calibration Lowest Point parameter for the

differential pressure (AI1 block). Apply an

actual input and confirm the value specified in

Calibration Lowest Point as the output value.

• Procedure to call up the calibration adjustment

parameter (Cal Cmd).

AI1 block : Cal Cmd : CAL_LOW
The present output is changed from 13.83 kPa

to 13.50 kPa in CAL_LOW of the differential

pressure (AI1 block) Cal Cmd parameter.

• Procedure to call up the calibration status

parameter (Cal Status).

AI1 block : Cal Status
Confirm the calibration status of CAL_

SUCCESS(1) using the Cal Status parameter.

DPharp

F0806.ai

25.00 kPa

0.00 kPa

Actual level

13.50 kPa

DPharp span: 0~25.00 kPa

Actual level: 13.50 kPa

Transmitter output: 13.83 kPa

Figure 8.4

Tank level measurement