8 output signal low cut mode setup, 9 impulse line connection orientation setup, 10 integral indicator display mode – Yokogawa EJX430B User Manual

Page 57: Output signal low cut mode setup -19, Impulse line connection orientation setup -19, Integral indicator display mode -19

Advertising
background image

<8. Setting Parameters>

8-19

IM 01C27B01-01EN

8.3.8 Output Signal Low Cut Mode Setup

Low cut mode can be used to stabilize the output

signal near the zero point.

( There is 10% of hysteresis at only point of

transition from low to high)
[Setup Low Cut Value]

• Procedure to call up the Lower cutoff* display

AI1 block: Lower cutoff*
Example: setup LOW_CUT of output to 15%
Lower cutoff*

= (“Eu at 100%” - “Eu at 0%”) × 0.15 + “Eu at 0%”

*: “Low Cutoff” is used instead of “Lower cutoff” for

Detachable antenna type (Amplifier housing code: 8 or

9).

[Setup Low Cut Mode]

• Procedure to call up the Low Cut Mode display

AI1 block: Low Cut Mode
Example: Low cut at 20%

(%)

50

20

0

50 (%)

For low cut in Linear mode

For low cut zero mode

[ sq root output ]

Example: Low cut 20%

Input

(%)

50

20

0

50 (%)

Example: Low cut 20%

F0804.ai

(%)

50

20

0

50 (%)

For low cut in Linear mode

[ Linear output ]

Example:

Low cut 20%

Output

Output

Input

Input

Output

Figure 8.3

Low Cut Mode

The low cut point has hysterisis so that the output

around the point is behaved as below figure.

<Example>

Output mode: Linear

Low cut mode: Zero

Low cut: 20.00%

Output

Setting range:

0 to 20%

Input

0%

(20%)

2%

Low

cut

point

Hystrersis fixed at 10%
of the cut point

F0805.ai

8.3.9 Impulse Line Connection Orientation

Setup

This function reverses the impulse line orientation.
Follow the procedure below to assign the high

pressure impulse line connection to the L side of the

transmitter.

• Procedure to call up the H/L Swap display

TRANSDUCER block: H/L Swap
Select Reverse among two choices ( Normal /

Reverse) in a H/L Swap parameter.

Normal is chosen at the time of shipment.

8.3.10 Integral Indicator Display Mode

It is easy to check on the LCD whether Non

Linearization or Sq root is set in the Linearization

Type parameter selected in the output mode for the

output signal.

When Linear is set in the Linearization Type

parameter, “√” is displayed on the integral indicator.

Advertising
This manual is related to the following products: