<8. Setting Parameters>

8-20

IM 01C27B01-01EN

8.3.11 Integral Indicator Scale Setup

The following three displays are available for the

integral indictor: differential pressure/pressure,

static pressure, and temperature. The following

three variables can be displayed on the integral

indicator: % of differential pressure range, % of

static pressure range, and % of temperature range.

Available displays

Description

and related parameters

% of range

(PRES %)

Indicates input pressure in –10 to

110% range depending on the set

range (

LRV and URV).

PRES % 45.6 %

% of static pressure

range (SP %)

*1

Indicates input static pressure in

–10 to 110% range depending on

the set range (

SP LRV and SP

URV).

SP % 52.6 %

*1:

Available for differential pressure transmitter.

Follow the procedure described in (1) to (2) below

to set the integral indicator.
(1) Display Selection
Display set to Display Selection is displayed on the

integral indicator.

• Procedure to call up the Display Selection

display

TRANSDUCER block: Display Selection

The Display Selection parameter enables

the differential pressure/pressure (AI1 block),

static pressure (AI2 block), and temperature

(AI3 block) to be displayed on the LCD. Select

whether or not to enable each block to be

displayed

(2) Cyclic Display
Information in the AI1 to AI3 blocks can be

displayed cyclically according to the display On/Off

setting for the differential pressure (AI1 block), static

pressure (AI2 block), and temperature (AI3 block)

selected in the Display Selection parameter.

8.3.12 Unit for Displayed Temperature

When the instrument is shipped, the temperature

units are set to

C (Centigrade). Follow the

procedure below to change this setting.

• Procedure to call up the Sensor Range.Units

Index display

AI3 block : Sensor Range.Units Index
Confirm that °C(deg C) is selected in the

Sensor Range.Units Index parameter for the

temperature (AI3 block).

Note: When the unit is changed by Sensor Range.Units Index

parameter in temperature ( Al3 block) , units of capsule

temperature is also changed.

8.3.13 Unit for Displayed Static Pressure

Follow the procedure to change the static pressure

unit.

Changing this parameter also changes the unit for

the static pressure display.

• Procedure to call up the Sensor Range.Units

Index display

AI2 block : Sensor Range.Units Index
Confirm that KPa is selected in the Sensor

Range.Units Index parameter for the static

pressure (AI2 block).

Monitoring the high or low static pressure of the

capsule depends on the setting of parameter

‘SP Select.’

• Procedure to call up the SP Select display

AI2 block: SP Select
Select High or Low in the SP Select parameter

for the static pressure (AI2 block).

Type of static pressure is set Absolute

pressure(Abs) at shipment.

When changing monitoring type of static pressure,

Follow below procedure.

• Procedure to call up the Static Press Type

display

AI2 block: Static Press Type
Select gauge pressure (Gauge) or absolute

pressure (Abs) in the Static Press Type

parameter for the static pressure (AI2 block).